CPU 01
3 Product Description
HI 800 189 E Rev. 1.01
Page 17 of 40
3.4.3.3 Communication
Indicators
Safe communication via safe
ethernet
is signaled by 2 small LEDs integrated in all RJ-45
connectors:
LED
Color
Status
Description
On
Full duplex operation
Blinking Collision
COL
Green
Off
Half duplex operation, no collision
On Connection
available
Tx
Yellow
Blinking Interface
activity
Table 7:
Indicators for safe
ethernet
Communication
Additionally, D-sub connectors and 2 corresponding LEDs are available for indicating non
safe communication via fieldbuses:
LED
Color
Status
Description
On
RS485, fieldbus 1 is active
FB1
Yellow
Blinking FB1 and FB2 blink simultaneously: Emergency loader is
active
On
RS485, fieldbus 2 is active
FB2
Yellow
Blinking FB2 and FB1 blink simultaneously: Emergency loader is
active
Table 8:
Indicators for Fieldbus Communication
3.4.4 Operating
System
The operating system loaded into the CPU contains all basic functions of the HIMatrix
programmable electronic system (PES), e.g.:
Reading the inputs and writing to the outputs
Processing the user program
Performing all test routines for hardware and software
Cycle time monitoring (watchdog)
Communication with other systems
For a description of the operating system functions and the variables used to configure the
systems and all modules, refer to the HIMatrix System Manual for the Modular F60 System.
3.4.5 User
Program
The user program is created using one programming tool, SILworX or ELOP II Factory. It is
then translated into a machine code using the code generator and transferred to the flash
EPROM of CPU module.
Summary of Contents for 98 2200126
Page 34: ...9 Disposal CPU 01 Page 34 of 40 HI 800 189 E Rev 1 01...