CPU 01
3 Product Description
HI 800 189 E Rev. 1.01
Page 19 of 40
TCP ports
Use
502
Modbus (can be modified by the user)
xxx
TCP SR assigned by the user
44818
Ethernet/IP Explicit Messaging Services
Table 11: Network Ports (TCP Ports) in Use
3.4.6.3
Connections for Fieldbus Communication
The 2 9-pole D-sub connectors can be accessed through the front plate of the module.
Designation
Hardware/ Fieldbus
submodule
Protocols
FB 1
(with module)
PROFIBUS master
PROFIBUS slave
RS485 module
RS232 module
RS422 module
INTERBUS master
PROFIBUS DP master
PROFIBUS DP slave
RS485 for Modbus (master or slave) and
ComUserTask
RS232 for ComUserTask
RS422 for ComUserTask
INTERBUS master
FB 2
(with module)
PROFIBUS master
PROFIBUS slave
RS485 module
RS232 module
RS422 module
INTERBUS master
PROFIBUS DP master
PROFIBUS DP slave
RS485 for Modbus (master or slave) and
ComUserTask
RS232 for ComUserTask
RS422 for ComUserTask
INTERBUS master
Table 12: Connections for Fieldbus Communication
The fieldbus submodules for communication via FB1 and FB2 are optional and must be
mounted by the manufacturer.
3.4.7 Pin
Assignments
The following tables describe the Pin assignments of the fieldbus connectors.
3.4.7.1
Pin Assignment of D-sub Connectors FB1 and FB2
with fieldbus submodule for PROFIBUS DP master or slave
Connection
Signal
Function
1
- - -
- - -
2
- - -
- - -
3
RxD/TxD-A
Receive/send data A
4 RTS Control
signal
5
DGND
Data reference potential
6
VP
5 V, plus pole supply voltage
7
- - -
- - -
8
RxD/TxD-B
Receive/send data B
9
- - -
- - -
Table 13: Pin Assignment of D-sub Connectors FB1 and FB2 for PROFIBUS DP
3.4.7.2
Pin Assignment of D-sub Connectors FB1 and FB2
with RS485 fieldbus submodule for Modbus master or slave and ComUserTask