Configuration
59/146
8.3.7.3
Scan and pairing
Ø
Select
IO-Link Wireless
Master
in the left column of the netFIELD
Wireless Web Server.
Ø
Open the
Scan
tab.
Figure 22: Scan tab
Use the Scan tab, to scan for unconnected devices.
Ø
Select
TxPower
.
The value range of “TxPower” (Transmission power) is “1 … 31” and the
default value “31”.
Ø
Click
Scan start
.
Ê
The system searches for unconnected devices. The scan result is being
displayed after a while.
Figure 23: “Scan tab”, scan result
Parameter
Description
Value, Value range
Index
Device index
0 … 20
Unique ID
Identification of the found IO-Link Device as unique ID
(
, 9 Bytes).
Copy/note the unique ID. This value is required for port
configuration.
0 … 0xFF
Slot Type
Slot type of the found device
Single slot, Double slot,
Default: Single slot
Revision ID
Revision ID of the found device
This parameter is specified by the found device. It
indicates software revision running on the found device.
0: No device connected,
Others: Software revision running on the
found device