Technical data
124/146
12 Technical data
12.1 Technical data device
Category
Parameter
Value
Product
Part number
1912.102
Model
NFD-3090-PNS-IOLM\W
Description
netFIELD IO-Link Wireless Master PROFINET IO-Device
Function
IO-Link Master Wireless for PROFINET IO with 2 tracks for
up to 16 channels
Communication
controller
Type
netX 90
Integrated memory
RAM
16 MB SDRAM
FLASH
8 MB
Ethernet
communication
Real-Time Ethernet
PROFINET IO-Device
Ethernet interface
Interface type
100BASE-TX, isolated
Auto-negotiation, Auto crossover
yes
Connectors
X31: Ethernet interface, M12, D-coded,
PROFINET IO port 1
X32: Ethernet interface, M12, D-coded,
PROFINET IO port 2
LEDs
System and application
SYS
System status
green/
yellow
APL
Application status
red/green
Power supply
1L (X21)
1L power supply (DC 24 V)
red/green
2L (X21)
2L power supply (DC 24 V)
red/green
PROFINET IO communication
SF
Status failure
red/green
BF
Bus failure
red/green
Ethernet
LINK (X31)
Link status, connector X31
green
ACT (X31)
Activity status, connector X31
yellow
LINK (X32)
Link status, connector X32
green
ACT (X32)
Activity status, connector X32
yellow
Wireless tracks
WT01 ...
WT03
IO-Link wireless track status,
antenna X1 … X3
red/yellow/
green
Wireless ports
WP01 ...
WP08
Port status,
wireless IO-Link ports 1 to 8
red/yellow/
green
WP09 ...
WP16
Port status,
wireless IO-Link ports 9 to P16
red/yellow/
green
Power supply 1L, 2L
Voltage supply
24V DC, –25%/+30% (18 V DC … 31.2 V DC)
Power consumption
1L: 0.2 A (at 24 V DC), 2L: 0.1 A (at 24 V DC)
Connectors
X21: Power supply input (Power In),
M12, L-coded
X22: Power supply output (Power Out),
M12, L-coded
Power consumption
(power connectors)
Max. 16 A, Max. current of the device including pass
through must not exceed 16 A for 1L and 2L. Observe
derating for the maximum current depending on the
ambient temperature.
Revers polarity protection
Yes
NFD-3090-PNS-IOLM\W | Hardware, installation and commissioning
DOC201101UM03EN | Revision 3 | English | 2022-02 | Released | Public
© Hilscher 2020 - 2022