AdaptaPAK® Maintenance and Troubleshooting
6 - TROUBLESHOOTING - COMPRESSOR LOW SUCTION PRESSURE
SYMPTOMS
SYMPTOMS
POSSIBLE ACTIONS
Low compressor
suction pressure
1. Lack of refrigerant
2. Evaporator dirty or iced
3. Clogged liquid line filter
drier
4. Clogged suction line or
compressor suction gas
strainers
5. Expansion valve
malfunctioning
6. Condensing
temperature is too low
7. Broken internal
compressor part
1. Check for leaks; repair
and add charge
2. Clean/Check Remote
3. Replace cartridge(s)
4. Clean strainers
5. Check and reset for
proper superheat
6. Check means for
regulating condensing
temperature
7. Fix component; repair
or replace compressor
7 - TROUBLESHOOTING - COMPRESSOR LOSES OIL
SYMPTOMS
SYMPTOMS
POSSIBLE ACTIONS
Compressor
loses oil
1. Lack of refrigerant
2. Excessive compression
ring blow-by
3. Refrigerant “flood back”
4. Improper piping or traps
1. Check for leaks, and
repair; add refrigerant
2. Replace compressor
3. Maintain proper
superheat at compressor
4. Correct piping