multiMAX™ Controller for AdaptaPAK®
J18 - Optional, Air Heat Reclaim, Normally Open Relay
J18: Air Heat Reclaim Valve
With this option, controller would close the relay and thus opening a valve to heat air in a heat exchanger.
J21 - Rack Alarm Output, Normally Open Relay
J21: Air Heat Reclaim Valve
If any rack alarm conditions are met, the controller will close the relay, activating rack alarms.
INPUTS
J1 - INPUT PWR, 24V AC/DC
J1: 24VAC Power to Controller
J2 -NTC/PRESS INPUTS
J2: Suction Pressure 1, Discharge Pressure, Drop Leg Pressure
J3 -TEMP INPUTS
J3: Suction Temperature 1, Ambient Temperature
J4 - 0-10VDC OUTPUTS
J4: 24 VAC Power, EC Fan Speed, Digital Compressor 1 Speed, Digital Compressor 2 Speed
J5 - 24V AC/DC DIGITAL INPUTS
J5: Rack Oil Alarm, Phase Loss Alarm 1, Receiver Level SW, Water Heat Reclaim
J6 - NTC/PRESSURE INPUTS
J6: Suction Temperature 2, Suction Pressure 2, Air Heat Reclaim