![Hillphoenix Adaptapak ADP-M0000-L0032 Installation And Operation Manual Download Page 53](http://html.mh-extra.com/html/hillphoenix/adaptapak-adp-m0000-l0032/adaptapak-adp-m0000-l0032_installation-and-operation-manual_2134298053.webp)
53
AdaptaPAK® Maintenance and Troubleshooting
c. Verify that all motors are mounted securely.
d. Lubricate motors, if applicable. Do not lubricate permanently sealed, ball bearing motors.
4. Inspect electrical wiring and components
a. Verify that all electrical and ground connections are secure; tighten as required.
b. Check condition of compressor and heater contacts. Look for
discoloration and pitting. Replace, as required.
c. Check operation and calibration of all timers, relays, pressure
controls and safety controls.
d. Clean electrical cabinet. Look for signs of moisture, dirt, debris, insects and wildlife. Take corrective action as
required.
e. Verify operation of crankcase heater by measuring amp draw.
5. Check refrigeration cycle.
a. Check suction, discharge and net oil pressure readings. If abnormal, take appropriate action.
b. Check pressure drop across all filters and driers. Replace, as required.
c. Verify that superheat at the compressor conforms to specification (i.e., 30°F to 45°F).
d. Check pre
ssure and safety control settings and verify proper operation.
Annually
Finally, once a year, perform the following checks:
1. In addition to quarterly and semi-annual maintenance checks, submit an oil sample for analysis.
a. Look for high concentrations of acid or moisture. Change oil and driers
until test results read normal.
b. Investigate source of high metal concentrations, which normally are
due to abnormal bearing wear. Look for
liquid refrigerant in
the crankcase, low oil pressure or low superheat
as a possible source.
2. Inspect suction accumulator (if equipped).
a. If the accumulator is insulated, remove insulation and inspect for leaks
and corrosion.
b. Pay close attention to all copper to steel-brazed connections.
c. Wire brush all corroded areas and peeling paint.
d. Apply an anticorrosion primer and paint, as required.
Re-insulate, if applicable.
Summary of Contents for Adaptapak ADP-M0000-L0032
Page 4: ...4 AdaptaPAK Parallel Refrigeration System ...
Page 20: ...20 AdaptaPAK Parallel Refrigeration System ...
Page 28: ...28 multiMAX Controller for AdaptaPAK ...