AdaptaPAK® Maintenance and Troubleshooting
1 - TROUBLESHOOTING - COMPRESSOR WILL NOT RUN (continued)
SYMPTOMS
SYMPTOMS
POSSIBLE ACTIONS
Compressor will
not run
9. Loose wiring
10. Phase loss monitor
inoperative
9. Check all wire
junctions and tighten all
terminal screws.
10. Turn power off at
disconnect switch
Swap any two of the
threee power input wires
Turn power on, indicator
light should glow and
compressor should start
Observe motor for
correct rotation
2 - TROUBLESHOOTING - COMPRESSOR NOISY/VIBRATING
SYMPTOMS
SYMPTOMS
POSSIBLE ACTIONS
Compressor is
noisy or vibrating
1. Flooding of refrigerant
into crankcase
2. Improper piping support
on suction or liquid line
3. Worn compressor
4. Scroll compressor
rotation reversed
1. Remove the
noncondensables
2. Remove excess
3. Open valve
4.. Rewire for phase
change