48
2.9 PV
:
Measurement
2
5
8
Grounding
terminal
ÐÖĞ
10
Terminal N
3
1
ÏÆÆ
7
ÏÎ
9
ÏÆÆ
String
(Black)
6
(Red)
4
• If there is any deteriorated
insulation performance be-
tween terminal P and ground
terminal, do not make any
measurements between ter-
minal N and ground.
• Connect the red test lead to
disconnect switch at the
string side.
Disconnector
Power conditioner, main switch
Terminal P
7.
Press the
MEASURE
key.
To make continuous measurements, pull out the key.
Note: Do not disconnect the test leads until a resis-
tance is indicated. If any of the lead is disconnected,
no accurate measurement is available.
8.
A resistance will be indicated after approximately four
seconds (updated every one second).
Note: If there is any deteriorated insulation perfor-
mance resulting in a resistance lower than a refer-
ence, do not make any measurement for terminal N of
the procedure
10
. Doing so may damage the solar
panel. Check the insulation resistance reference in
advance with safety standards.