Installation and Operating Instructions for Heta SL800 Aqua stove Pevex1018/AH/ver1:Jan 2013

never be less than 175 cm

2

, which 

corresponds to a diameter of 150 mm. 

If a damper is fitted in the flue gas 

pipe, there must always be at least 

20 cm

2

 of free passage, even when 

the damper is in its “closed” position. 

Wood-burning stoves must never 

be connected to chimneys that are 

also linked to a gasfired heater.

 An 

efficient stove makes high demand on 

chimney properties – so always have 

your local chimney sweep evaluate 

your chimney.

Connection to a brick chimney

Brick a thimble into the chimney and 

seat the flue gas pipe in this. The 

thimble and flue gas pipe must not 

penetrate the chimney opening itself, 

but must be flush with the inside of 

the chimney duct. Joins between 

brickwork, the thimble and flue gas 

pipe must be sealed with fireproof 

material and/or beading

Connection to a steel chimney

When fitting a connection from a 

top-output stove directly to a steel 

chimney, we recommend fitting the 

chimney tube inside the flue gas spi-

got so that any soot and condensation 

drops into the stove itself rather than 

collecting on the exterior surface of 

the stove. 

For connections to chimneys that are 

run through ceilings, all national and 

local regulations regarding distance to 

flammable material must be followed. 

It is important that the chimney is 

fitted with roof support so that the top 

panel of the stove is not required to 

bear the entire weight of the chimney 

(excessive weight may cause damage 

on or noise from the stove).

Draft conditions

Poor draft may result in smoke being 

emitted from the stove when the door 

is opened. The minimum chimney 

draft to ensure satisfactory combu-

stion in stoves of this kind is 12 PA. 

However, there will still be a risk of 

smoke emission if the firing door is 

opened during powerful firing. The flue 

gas temperature at nominal output is 

182°C when expelled to an exterior 

temperature of 20°C. The flue gas 

mass flow is 6.3 g/sec. The chimney 

draft is generated by the difference 

between the high temperature of the 

chimney and the low temperature of 

the fresh air. The length and insulation 

of the chimney, wind and weather 

conditions also have an effect on the 

ability of the chimney to generate ap-

propriate under-pressure.

If the stove has not been used in a 

while, check that the chimney and 

stove are not blocked with soot, bird 

nests, etc., before using it.

Reduced draft can occur 
when:

•  The difference in temperature 

is too small – due to insufficient 

chimney insulation, for example.

•  The outdoor temperature is too 

high – in summer, for example.

•  No wind is blowing. 

•  The chimney is too low and shel-

tered.

•  The chimney contains false air.

•  The chimney and flue gas pipe are 

blocked.

•  The house is too airtight (i.e. when 

there is an insufficient supply of 

fresh air).

•  Poor smoke extraction (poor draft  

conditions) due to a cold chimney 

or bad weather conditions can be 

compensated for by increasing 

the airflow into the stove.

Good draft occurs when:

•  The difference in temperature 

between the chimney and outdoor 

air is high.

•  The weather is fine. 

•  The wind is blowing strongly.

Summary of Contents for SCAN-LINE 800 AQUA

Page 1: ...ns for Heta SL800 Aqua stove Pevex1018 AH ver1 Jan 2013 www heta dk SCAN LINE 800 AQUA APPROVED FOR USE IN SMOKE CONTROL AREAS WHEN BURNING DRY WOOD LOGS OR AUTHORISED FUELS OPERATING INSTRUCTIONS GB...

Page 2: ...the floor area must match national and local regulations The chimney connection The chimney opening must follow national and local regulations Howe ver the area of the opening should of specifications...

Page 3: ...e weight of the chimney excessive weight may cause damage on or noise from the stove Draft conditions Poor draft may result in smoke being emitted from the stove when the door is opened The minimum ch...

Page 4: ...me correct firing prevents environ mental damage in the form of smoke and emmissions and also reduces the risk of chimney fires If the wood is wet and inadequately seasoned a large proportion of the e...

Page 5: ...top position fig 1 Reduce combu stion airflow gradually by lowering the handle When the handle is in the lowest position fig 2 combustion airflow is completely closed Fig 1 Fig 2 Open Closed The SL80...

Page 6: ...go out a red hot ember bed will be left and further wood can be added 6 Place 2 3 logs on the ash bed ensu ring that the wood is not stacked too closely and with the adjust the side airslider to fully...

Page 7: ...air controls or dampers left open except as directed in the instructions Refuelling A fresh supply of fuel should nor mally be added while there is still a good layer of hot embers Spread the embers...

Page 8: ...ary and se condary air in these instructions we call this combustion air The stove provides excellent heating efficiency and the window is easy to maintain as the secondary air flushes the surface of...

Page 9: ...ith wet wood In this case much of the heating energy is used to dry the wood resulting in poor heating eco nomics and an increased risk of soot deposits in the chimney OPERATIONAL PROBLEMS MAINTENANCE...

Page 10: ...the dealer Therefo re the stoves are guaranteed against defects in manufacturing FOR FIVE YEARS This guarantee does not cover Wea ring parts fragile parts such as The fire proof bricks in the combu s...

Page 11: ...ns for Heta SL800 Aqua stove Pevex1018 AH ver1 Jan 2013 Connection of external air flow fresh air through the floor on Scan Line 800 Aqua When connection external air flow use a 100 air conduit for in...

Page 12: ...Operating Instructions for Heta SL800 Aqua stove Pevex1018 AH ver1 Jan 2013 4 5 6 7 Emptying the ash pan fig 4 7 Cleaning after sweeping the chimney and replacing the stones Fig 8 14 Scan Line 800 Aqu...

Page 13: ...etween the cooling pipes lies as as sembled on the picture as when you receive it from Heta otherwise it will result in great loss of efficiency and raise the temperature of the chimney Tip the top pl...

Page 14: ...AH ver1 Jan 2013 Connection water to Scan Line 800 Aqua Fig 20 Bleed screw SYR Temperature valve pkt 5 Forward motion warm 1 2 RG point 4 12 mm copper pipe for water connection point 1 Return cold 1 2...

Page 15: ...sure The SYR valve point 5 is an extra safety device which opens by a tem perature over 95 in the boiler Connect cold water pressure on maxi mum 15 on the water connection point 1 make sure that your...

Page 16: ...d In Scotland and Wales this power rests with Ministers in the de volved administrations for those coun tries Separate legislation the Clean Appendix A Air Northern Ireland Order 1981 ap plies in Nort...

Reviews: