9
Fault reports and their corrections
60
Betriebsanleitung_commotherm_5_15_SW_WW_Touch_Englisch_V1.2
No.
Fault report
Cause of fault
Fault correction
200 HP flow sensor
Failure
Heat pump-flow sensor
Check sensor, replace as necessary
Check plug, replace as necessary
Check wiring incl. Connections,
replace as necessary
✆
- contracting party
201 HP back flow sensor
Failure
Heat pump-back flow sensor
Check sensor, replace as necessary
Check plug, replace as necessary
Check wiring incl. Connections,
replace as necessary
✆
- contracting party
202 HP source input sensor
Failre source input temperature
sensor
Check sensor, replace as necessary
Check plug, replace as necessary
Check wiring incl. Connections,
replace as necessary
✆
- contracting party
203
HP source output
sensor
Failre source output temperature
sensor
Check sensor, replace as necessary
Check plug, replace as necessary
Check wiring incl. Connections,
replace as necessary
✆
- contracting party
204 HP hot gas sensor
Failure hot gas sensor of the
refrigerant circuit
Check sensor, replace as necessary
Check plug, replace as necessary
Check wiring incl. Connections,
replace as necessary
✆
- contracting party
205 HP source temp. low
Failure source pump
System pressure too low
Exhausted source
Function control source pump
Check system pressure
✆
- contracting party
206
HP high pressure
triggered
Der Druck ist außerhalb des
definierten Bereiches, indem der
Verdichter arbeiten soll.
Function control condensator pump
(heating pump)
✆
- contracting party
207
HP low pressure
triggered
The pressure is outside of the
range where the compressor
should work.
Failure source pump
Lack of refrigerant
Failure source output sensor
Visual Control of the refrigerant
control regarding leakage
✆
- contracting party
208 HP max. temp. reached
´The flow temperature of the heat
pump has reached the max.
temperature.
Check HP paramter (Max. Temp may
not be higher than 58°C).
✆
- contracting party
209 HP softstarter
Rotating field direction is false
(left instead of right)
Phase error
Phase is missing
✆
- contracting party
210 HP evaporator
Error is currently not taken!
-
211 HP refrigerant sensor
Failure refrigerant sensor of the
refrigerant circuit
Check sensor, replace as necessary
Check plug, replace as necessary
Check wiring incl. Connections,
replace as necessary
✆
- contracting party
212 HP max. hot gas temp.
Maximum hot gas temperature of
125°C was reached.
✆
- contracting party
213 HP hot gas compr. start Error is currently not taken!
-
214
HP water pressure too
low
System pressure too low
✆
- contracting party