Fault reports and their corrections
9
Betriebsanleitung_commotherm_5_15_SW_WW_Touch_Englisch_V1.2
59
No.
Fault report
Cause of fault
Fault correction
031
ANTIFREEZE HOT
WATER TANK
Too low temperature in the hot
water tank
Antifreeze function
is activated
Display only, no action required.
032
ANTIFREEZE
HEATING CIRCUIT
Too low temperature in the
heating circuit
Antifreeze
function is activated
Display only, no action required.
033 ANTIFREEZE SOLAR
Too low temperature in the solar
tank
Antifreeze function is
activated
Display only, no action required.
034
ANTIFREEZE HYDR.
COMPENSATOR
Too low temperature in the
hydraulic
compensator
Antifreeze function is activated
Display only, no action required.
037
HOT WATER TANK
LOADING
Hot water tank didn´t reach set
temperature during loading time;
hot water tank loading gets
blocked till fault correction
Adapt loading time
Activate hot water tank priority
Check hydraulic system
038 MAINTENANCE
This fault text occurs after 1000
operating hours
Fault has to be receipted by an
authorized person:
Settings
Enter Code
039 SERVICE
This fault text occurs after 3000
operating hours
Carry out boiler system maintenance
by authorised personnel
044
LEGIONELLA
PROTECTION
Tank thermal disinfection active
Tank will be heated up to 70
°C
Display only, no action required.
046 MOD.ERR EXT.
Communication error of CAN 2 to
external module
Check module CAN connection
Check module
✆
- contracting party
047 MOD.ERR INT.
Communication error of CAN 1 to
external module
Check module CAN connection
Check module
✆
- contracting party
049
DATAERROR
MEMORY EXTERNAL
Data adjustment error at external
module
✆
- contracting party
050
DATAERROR
MEMORY INTERNAL
Data adjustment error at internal
module
✆
- contracting party
053
ADDITIONAL FLUE
GAS SENSOR
Additional boiler flue gas
temperature out of range
Check sensor, replace as necessary
Check plug, replace as necessary
Check wiring incl. Connections,
replace as necessary
054
EXTERNAL SET
POINT
No
Signal
of
external
requirement or control (if line
monitoring is active)
Check sensor, replace as necessary
Check plug, replace as necessary
Check wiring incl. Connections,
replace as necessary
056 SCREED BAKE OUT
Failure at screed bake out; Flow
set temperature could not be
reached
Function check mixer with mixer
motor
Function check pump
Check sensor position
Required heat output to high
057 CHECK DATA MODUL
Module parameter is not in the
specified range
Check module parameter
Restart T-Control
072 CAN FAULT
Failure CAN Bus
✆
- contracting party
077 ADDITIONAL INPUT
Additional input (e.g.: system
pressure, CO-sensor) active
Check
failure
additional
input
aggregate