T-Control
38
Betriebsanleitung_commotherm_5_15_SW_WW_Touch_Englisch_V1.2
T
im
e
m
od
e
B
uf
fe
r
H
ot
w
at
er
ta
n
k
H
ea
ti
n
g
c
ir
cu
it
S
ol
ar
H
ea
t
pu
m
p
N
et
p
um
p
H
yd
r.
c
o
m
pe
ns
.
Z
on
e
va
lv
e
E
xt
.
re
qu
ire
m
en
t
Term
Description
Unit
Flow fixed
temperature
Setting up the flow temperature during the set heating time (operation
mode “flow fixed”)
°C
Room influence
Room influence influences the flow temperature as a function of the
room temperature:
Depending on the level of this value, the difference of required room-
and room set temperature exerts more influence on the calculation of
the flow set temperature.
-
Correction
The correction influences respectively adjust the flow set temperature:
This value gets multiplied by 2 and added to the flow set temperature
°C
Kneeling influence
Setting up the factor of the lowering temperature influence
-
End run
Setting up the outside temperature which conducts a permanent running
of the pump to avoid freezing.
°C
Parameter II
Switching temperature
Setting up the switching temperature. That´s the average daytime
temperature that conducts the switching between winter set temperature
and summer set temperature. A higher level of the switching
temperature will delay the switching to summer operation.
°C
Temp. increase
Setting up an increase of the required heat circuit temperature
Compensates heat loss between buffer and heat circuit by exceeding
the hot water tank set temperature
High heat loss assumes a higher value
°C
Outside temp. sensor
Selection of the outside temperature sensor
If multiple outside temperature sensors are installed, the desired one
can be assigned to the chosen heat circuit.
-
Balancing outside
sensor
Adjusting the balancing of the outside temperature sensor
Adjustment with a reference thermometer (actual outside
temperature)
°C
Hot water tank priority
Activation hot water tank priority (ON/OFF)
The hot water tank is loaded prior compared to the heating circuit.
-
Kneeling barrier
Activation kneeling barrier (ON/OFF)
Heating circuit gets locked during permanent reduction respectively
beyond heating time
-
Heat curve settings
Flow max.
temperature
Setting up the maximum flow temperature of chosen heating circuit
°C
Root point
temperature
Setting up the minimum flow temperature of chosen heating circuit
°C
Flow temperature at
+10°C
Setting up the flow temperature of chosen heating circuit at +10°C
outside temperature
°C
Flow at adjustable
outside temperature
Setting up the flow temperature of chosen heating circuit at a adjustable
outside temperature
°C
Adjustable outside
temperature
Setting up the outside temperature of chosen heating circuit regarding
flow set temperature
°C
Actual outside
temperature
Indicates the actual outside temperature
°C
Switch off temperature
Setting up the outside temperature regarding deactivation of chosen
heating circuit
°C