5.Operational setting
5.Operational setting
To set the “TW-510R”, use the Set switch at center of front side of machine.
Loosen the cover screw and remove the cover before setting.
5-1.To set the ID
Set the same ID as the one of TW-510T.
To set the ID, use the 8-
verse DIP Switch 1(DIPSW1). The ID is normally represented by “0”
to “255” in decimal notation; however, for setting into this machine, convert it into the binary
notation.
Carry out setting according to the Setting conversion table (appendix 1).
ID1: 0 to 255
●
For “TW-510R-W”/”TW-510RDW” model,
For ”
RW
”/”
RDW
”model as an option, you can set the ID2 in addition to the normal ID1. To
set the ID2, use the 8-verse DIP Switch 2 (DIPSW2).
ID2: 0 to 255
For “TW-510R” model, the setting of DIPSW2 is disabled.
For “TW-510R
W
”/”TW-510R
DW
” model, if ID1 and ID2 are set to the same contents,
signal turns on only through the Output terminal block
1
.
Be sure to turn off the power supply before changing the setting.
SW for ID1
SW for ID2
SW for each operation
SW for relay output time
SW for double counting
prevention time