Always switch off the mains power supply before making any connections!. Electrical connections should be carried out by a

competent person, if in doubt consult a qualified electrician!

Cables should enter the control unit through the cable glands fitted to the bottom of the RS1 unit.

5.1  POWER - The 240v A/C input should be connected from an adjacent 13 amp 3 pin switched socket.The plug must be fitted with a 5 amp fuse.

Connect to terminals marked L, N, E, MAINS

5.2  MOTOR - Connect the motor lead to the terminals marked E,L1,L2 N3 MOTOR. The blue motor neutral cable must be connected to the

terminal marked N3. Connect the yellow/green earth cable to the terminal marked E. Connect the brown and black motor power cables to terminals

L1 & L2. Ensure that motor direction matches the open and close LED’S if necessary interchange the motor cables at terminals L1 & L2.

5.3  ADDITIONAL LIGHTING - Terminals marked LIGHT, E, L, N, provide a 240 volt ac output which functions the same as the built on light.

Lighting switches on for 4 minutes whenever the door is operated and turns off automatically. Maximum load 200 watts. The output should be

connected to a class 2 double insulated luminaire.

5.4  PHOTOELECTRIC SAFETY BEAM - ANSA RS1 can be connected to one or two photoelectric sensors which must be capable of

operating from a 24v DC supply voltage, and must have a normally closed NPN output signal. If two photocells are used they should be the same type.

OPERATION - The safety beam has no effect on an opening door. Breaking the safety beam prevents closure of an open door, and will also stop

and re-open a closing door.

CONNECTING A SINGLE PHOTOELECTRIC CELL - Remove the factory fitted ling connecting -VE & S1. The supply to the photocell is

connected to the terminals marked -VE & +VE. Connect the output signal to terminal S1, (retain the link connecting S1 & S2).

CONNECTING TWO  PHOTOELECTRIC  CELLS - Remove the factory fitted ling connecting -VE & S1 and S1 & S2. The supply to the

photocell is connected to the terminals marked -VE & +VE. Connect the output signal from the first sensor to terminal S1. Connect the output signal

from the second sensor to terminal S2.

5.5  OPTIONAL DOOR CONTROLS - A wide range of additional door controls may be connected to the unit, i.e. key switches, push buttons,

digital key pads etc.

IMPULSE DEVICE - A push to make (normally open) push button or key switch can be connected to terminals COM & IMP, this provides an

OPEN - STOP - CLOSE - STOP sequential operation.

STOP PUSH BUTTON - A push to break (normally closed) push button or key switch can be connected to terminals marked COM & STP.

Activation will stop the door immediately regardless of it’s position. If used remove the factory fitted link connecting COM & STP.

DOOR OPEN DEVICE - A push to make (normally open) push button can be connected to terminals COM & OPN. Operation will open the

door or re-open a closing door.

DOOR CLOSE DEVICE - A push to make (normally open) push button can be connected to terminals COM & CLO.To provide a door close signal.

- Electrical Connections

Summary of Contents for Ansa RS1

Page 1: ...are suitable for the application and are all working satisfactorily This will permit the nominated person to attach a CE label identifying the name of the installing company a unique door reference nu...

Page 2: ...Installation Instructions Insulated roller door and Compact insulated roller door remote control unit March 2007 Insulated Roller Garage Doors...

Page 3: ...e read these instructions carefully prior to commencing installation of the unit Operate unit only when the door is in full view and free from any obstruction No one should enter or leave the garage w...

Page 4: ...lectronics monitor the motor drive and limit switches and turn off the motor run timer as soon the door reaches a fully open or a fully closed position There is no need to wait for the run time to exp...

Page 5: ...s are used they should be the same type OPERATION The safety beam has no effect on an opening door Breaking the safety beam prevents closure of an open door and will also stop and re open a closing do...

Page 6: ...close circuit board LED S if necessary switch off the mains power supply and interchange the motor cables at L1 and L2 Note the motor unit has an inbuilt thermal trip which activates if the motor get...

Page 7: ...Figure 6 Connection diagram Installing 2 photoelectric cell units Figure 7 Connection diagram Option controls...

Page 8: ...important that the photo beam is centred on the reflector using the following set up procedure Adjust fixing screws A B so that the photoelectric sensor and pivot bracket can be moved up and down and...

Page 9: ...en switched on selects partial retract If the photocell is activated the door retracts 200mm instead of returning to the fully open position 10 3 Dip switch 3 Security When switched on extends the mot...

Page 10: ...ig 3 In some instances it may be helpful to switch off the controls operating the door temporarily without turning off the mains power supply or erasing transmitter security codes For example during h...

Page 11: ...nk wire interconnecting terminals Com Stp if fitted If a stop control device is fitted check the operation and condition of cables connecting this to terminals Com Stp 17 3 Faulty operation the Red in...

Page 12: ...e Engineer Comments Technical Specification 18 SupplyVoltage 220 240VAC Transformer Power 3VA Power Relays 12 A 230VAC OperatingTemperature 15 to 55 deg C Enclosure Rating IP 44 Courtesy light 40 watt...