- Troubleshooting  Guide

Note ;Always switch off the power supply before attempting to repair the door or control system.!

Faulty operation -- Red indicator LED is off - see 17.1.
Faulty operation -- Red indicator LED is on - see 17.2
Faulty operation -- Red indicator LED is flashing quickly - see 17.3
Faulty operation -- Red indicator LED is flashing slowly - see 17.4
Remote control transmitter problems - see 17.5

17.1 Faulty operation, the Red indicator LED is off. This indicates a power failure problem.
Check the power supply is live at the socket outlet.
Check the fuse in the 13a plug and fit a new 5A fuse if necessary.
Check both control board fuses, spares are supplied, fitted to the control unit cover. The main PCB fuse is a T 5 A 250 V [dia 5 mm x
20 mm , --see Fig 3]. The control PCB fuse is a T 500 Ma 250 V [dia 5mm x 20 mm , -- see Fig 3]
Check the security of the mains power cable at terminals L,N and E. If no fault is found, repair or replace the control board.

17.2  Faulty operation, the Red indicator LED is on. This indicates a possible problem with the motor drive.
Temporarily switch on and check the control board status LED -- if this is green:-  The motor thermal trip may have operated. wait ten minutes
for the motor to cool down. Switch off and check the security of the motor cables at terminals E,L1,L2 and N3.
Check the motor drive and limit switches.If the control board status LED is red ;- Check the security of the link wire interconnecting terminals
Com & Stp [if fitted]. If a stop control device is fitted, check the operation and condition of cables connecting this to terminals Com & Stp.

17.3  Faulty operation , the Red indicator is flashing quickly. This indicates that the safety circuit is active.
Clean the photoelectric sensor and reflector.
Check the alignment of the safety beam.
Check the condition of cables connecting sensor[s] to terminals Ve, +Ve, S1 & S2. If a single photoelectric sensor is fitted check the
security of the link interconnecting terminals S1 & S2.
Operate the door using the photocell override procedure see section 12 and if necessary renew a damaged sensor or reflector.

17.4  Faulty operation , the Red indicator is flashing slowly. This indicates that the self-test diagnostic circuit has activated.
Check that terminals Com & Stp are interconnected using a link wire or stop push button before switching the mains power supply on.
Check that operating button next to the Red LED “clicks” when pressed.
Check for short circuits in any control devices or cables connected to terminals Com, Imp, Opn and Clo. [if fitted].
The photoelectric sensor may be faulty disconnect sensor[s] and temporarily bridge terminals -Ve & S1 and S1& S2.
Switch off the power supply for 5 seconds and re-power the unit to reset the system. If no fault is found, repair or replace the control
board.

17.5  Remote control transmitter problems.
The red LED on the hand set should illuminate when the button is pressed, if it does not- replace the battery in the transmitter. If the
LED is dim the battery is low and the operating range will be reduced.

Summary of Contents for Ansa RS1

Page 1: ...are suitable for the application and are all working satisfactorily This will permit the nominated person to attach a CE label identifying the name of the installing company a unique door reference nu...

Page 2: ...Installation Instructions Insulated roller door and Compact insulated roller door remote control unit March 2007 Insulated Roller Garage Doors...

Page 3: ...e read these instructions carefully prior to commencing installation of the unit Operate unit only when the door is in full view and free from any obstruction No one should enter or leave the garage w...

Page 4: ...lectronics monitor the motor drive and limit switches and turn off the motor run timer as soon the door reaches a fully open or a fully closed position There is no need to wait for the run time to exp...

Page 5: ...s are used they should be the same type OPERATION The safety beam has no effect on an opening door Breaking the safety beam prevents closure of an open door and will also stop and re open a closing do...

Page 6: ...close circuit board LED S if necessary switch off the mains power supply and interchange the motor cables at L1 and L2 Note the motor unit has an inbuilt thermal trip which activates if the motor get...

Page 7: ...Figure 6 Connection diagram Installing 2 photoelectric cell units Figure 7 Connection diagram Option controls...

Page 8: ...important that the photo beam is centred on the reflector using the following set up procedure Adjust fixing screws A B so that the photoelectric sensor and pivot bracket can be moved up and down and...

Page 9: ...en switched on selects partial retract If the photocell is activated the door retracts 200mm instead of returning to the fully open position 10 3 Dip switch 3 Security When switched on extends the mot...

Page 10: ...ig 3 In some instances it may be helpful to switch off the controls operating the door temporarily without turning off the mains power supply or erasing transmitter security codes For example during h...

Page 11: ...nk wire interconnecting terminals Com Stp if fitted If a stop control device is fitted check the operation and condition of cables connecting this to terminals Com Stp 17 3 Faulty operation the Red in...

Page 12: ...e Engineer Comments Technical Specification 18 SupplyVoltage 220 240VAC Transformer Power 3VA Power Relays 12 A 230VAC OperatingTemperature 15 to 55 deg C Enclosure Rating IP 44 Courtesy light 40 watt...

Reviews: