Helvar 458/CTR8 8-Channel Ballast Controller Module: Installation and User Guide

Installation

Loosen 

knobs

Blanking 

plate

Unscrew and remove the blanking plate(s) from the chassis.

Note 1:

 

458M1: 1 blanking plate

 

458M2: 2 blanking plates

 

458M3: 3 blanking plates

Note 2:

 

The diagrams on this page show the 458M1/4S10 Chassis. 

Covers and knockouts are removed from the 458M2 and 458M3 in a 

similar way.

1.2  Remove chassis blanking plates

For details, refer to the 458Mx Chassis Installation Guide.

1.1  Remove chassis cover

Partially unscrew the two knobs on the module to reveal the pins.

1.3  Loosen attachment knobs

Attach the module to the chassis by slotting the pins of the module to the 

mounting bracket.

1.4  Slot module pins into mounting bracket 

Screw the knobs to the mounting bracket to secure the module.

1.5  Tighten knobs

1.  Attach the module to a chassis

Mounting, environmental and clearance requirements

Mounting

•  Attach the 458/CTR8 to a 458M1, 458M2, or 458M3 chassis that is mounted vertically on a flat surface.

Environment

•  The ambient temperature must be between 0 °C and +40 °C.
•  Air humidity must be between 0 % and 90 % (noncondensing).
•  The area must be adequately ventilated.
•  Do NOT install this product in a damp location.

Clearance

•  For effective ventilation, ensure that there is adequate space around the combined chassis and module(s): 50 mm 

above, below and on both sides. Refer to the mounting dimensions and clearance diagrams in the 458Mx Chassis 

Installation Guide.

•  When a Helvar control module (e.g. 458/CTR8) is attached, the grilles must NOT be obstructed.
For further information, refer to the Helvar 458Mx Chassis Installation Guide.

Warning:

  Before attaching the module and making any connections, make sure that the mains supply is isolated.

Important:

  The module may be controlled by either DALI or SDIM/DMX, but DALI and SDIM/DMX must not be connected 

simultaneously.

Summary of Contents for 458/CTR8

Page 1: ...Helvar Data is subject to change without notice www helvar com i Installation and User Guide 458 CTR8 8 Channel Ballast Controller Module ...

Page 2: ...ons 4 4 Replace the chassis cover 4 5 Power on the unit 4 Load types 5 Control Panel 5 Control Panel functions 5 Control Panel LCD Display 6 Control Panel Keypad 6 Adjusting channel and output levels with the Control Panel Keypad 7 Navigating the menu with the Control Panel Keypad 7 Physical selection 8 Menu options 9 Main menu 9 Menu options details 10 Error messages 15 Dimensions mm 15 Technical...

Page 3: ... out prior to the fitting of the control modules which prevents possible damage to the control modules due to circuit overload or faults or to the use of high voltage insulation testing equipment LCD display and keypad The front of the module is equipped with an LCD display and keypad to set basic configuration parameters and provide basic control of channel and output levels For information see C...

Page 4: ... the module to a chassis Mounting environmental and clearance requirements Mounting Attach the 458 CTR8 to a 458M1 458M2 or 458M3 chassis that is mounted vertically on a flat surface Environment The ambient temperature must be between 0 C and 40 C Air humidity must be between 0 and 90 noncondensing The area must be adequately ventilated Do NOT install this product in a damp location Clearance For ...

Page 5: ... the 458M2 and 458M3 2 Connect power and load cables to module sockets 1 2 3 4 5 6 7 8 TO OUTPUT 6 TO CH6 MCB CTRL 1 2 3 4 5 6 7 8 OUTPUTS MCB BLOCK TO CH1 MCB TO OUTPUT 1 N L TO OUTPUT 2 TO CH2 MCB TO OUTPUT 4 TO CH4 MCB TO OUTPUT 5 TO CH5 MCB TO OUTPUT 7 TO CH7 MCB TO OUTPUT 8 TO CH8 MCB TO OUTPUT 3 TO CH3 MCB SDIM DMX cable loom Bypass terminals Output control terminals SDIM DMX 1 0 V 2 5 7 0 V...

Page 6: ...terminals to enable the cable termination Note The module can be used for 0 10 V Source 1 10 V Sink PWM PWM reverse DALI Broadcast and DSI Control Output control terminals 1 10 V Ballast DALI DSI PWM Ballast 3 4 Output control connections Connect the required output control connections to the output control terminals of the module The following diagram shows an example 4 Replace the chassis cover ...

Page 7: ...ters with the Control Panel DMX addresses Channel pairing Output mode Minimum fade time Override level Switch on level Other parameters can be set using Designer software DALI connection Example to Helvar 920 Routers Adjust the following parameters with the Control Panel Channel pairing Minimum fade time Override level Other parameters can be set using Designer software Control Panel DALI standalo...

Page 8: ... channel s or output s ALL is displayed here if all channels or outputs are selected simultaneously but are set to different levels Main Display Screen The Main Display Screen appears When the 458 CTR8 is powered on After 60 seconds of inactivity on the Control Panel After exiting the Control Panel options SDIM DMX Activity and DALI Power Activity indicator This indicator in the top left hand corn...

Page 9: ...ht level 3 Adjust lighting level percentage for the selected channel s 4 Return to the Main Display Screen Follow these steps to adjust channel and output levels Navigating the menu with the Control Panel Keypad Follow these steps to access and navigate the menus 1 From the Main Display Screen Press UP or DOWN to access the menu options 2 Scroll through main options 3 Select an option access optio...

Page 10: ...physical selection mode 1 Put the piece of equipment e g router sensor etc into physical selection mode refer to the manufacturer s instructions 2 From the Main Display Screen Press either RIGHT or LEFT to access the relay and output channel levels 3 Step left or right through channels to select the channel that you want to use for physical selection 4 Press UP or DOWN to physical select the chann...

Page 11: ...enes Reset DALI scenes to default settings Groups Group and ungroup relay and ballast channels Min fade time Set minimum fade times for relay and ballast channels Power on level Set DALI power on levels for relay and ballast channels Failure level Set or disable DALI failure levels for relay and ballast channels Override level Set or disable override levels for relay and ballast channels Minimum l...

Page 12: ...abled Default 1 DMX address 1 512 Disabled Default 1 DALI base DALI Base 1 57 Default 1 DALI addresses Channel 1 8 Address 1 64 Removed Disabled Removed Next time you connect it to a controller program or router the DALI address will be reallocated Disabled The address will not be reallocated Ballast output Submenu items Options Status read only No ballast outputs present Refresh Rechecks status o...

Page 13: ... of any combination of channels This option is always available even when password protection is applied to other options Range Scene 1 16 Save as scene The levels that are currently active for all channels are applied to this scene You can recall stored scenes in the Recall Scene menu see above Range Scene 1 16 Default scenes Default lighting scenes can be applied to the output channels i e scene...

Page 14: ...chPanel not with the Control Panel Options Channel 1 8 ALL Power on level 0 100 Last Default in DALI mode 100 Failure level Set channel levels for situations where the DALI bus goes low such as when it is short circuited or when the DALI PSU is turned off Options Channel 1 8 ALL Failure level 0 100 do not apply Failure level Default 100 Override level If the override input connection is short circ...

Page 15: ... affects the level at which the channel turns off When hysteresis is on the switch off level is 80 of the switch on level At or below the switch off level the channel will be off For example if the switch on level is 50 and the signal rises to this level or above the channel will turn on Then if the signal falls to 40 or below the channel will turn off By default When hysteresis is on and the sign...

Page 16: ...use the following functions menus Change output levels View technical information about the module Recall a scene Enter the password If you chose to use the password after one minute of inactivity the Control Panel goes to standby and the Enter password menu appears in Main menu Use password disables the functionality of the remaining menus You can access the menus but cannot change any settings u...

Page 17: ...nd their meanings Error messages Message Reason Output Trip Notes Override On Override input pulled low Override level User can change override levels on the fly unless locked Comms Error SDIM communications error e g two units with the same SDIM address or incorrect SDIM DMX mode selection Ballast O P 458 OPT4 options module connected The 458 OPT4 module should not be connected Dimensions mm ...

Page 18: ...00 VAC 240 VAC nominal 85 VAC 264 VAC absolute 45 Hz 65 Hz Power consumption 1 2 W excluding loads Protection Power circuit protection 6 A max external protection earth mandatory Thermal protection Control board resettable fuse Installation Mounting Attached to 458M1 458M2 or 458M3 chassis Mechanical data Dimensions 105 mm 360 mm 170 mm Housing Powder coated steel black Weight 2 2 kg IP code IP20 ...

Reviews: