12 Helvar 458/CTR8 8-Channel Ballast Controller Module: Installation and User Guide
Min. fade time
Set the minimum time it takes to change between minimum and maximum lighting levels.
Options:
Channel:
1– 8,
ALL
Fade time:
0: 20 ms
1: 150 ms
2: 500 ms
3: 1 s (Default)
Power on level
Set the level each channel will go to when the unit is powered on, with DALI connected.
Note:
Power-on levels for SDIM are set in the router or TouchPanel (not with the Control Panel).
Options:
Channel: 1–8;
ALL
Power on level: 0 % – 100 %;
Last
(Default in DALI mode: 100 %)
Failure level
Set channel levels for situations where the DALI bus goes low, such as when it is short-circuited or when the DALI PSU
is turned off.
Options:
Channel: 1–8;
ALL
Failure level:
0 % – 100 %; **** (= do not apply Failure level); (Default:100 %)
Override level
If the override input connection is short-circuited, e.g. by contact closure on an alarm system, all channels are set to
their override level, regardless of external control signals.
Options:
Channel: 1–8;
ALL
Override level: 0 % – 100 %; **** (= do not apply override level); (Default:100 %)