6.1 Arrangement of smoke detectors in corridors and hallways
and in special spatial geometries
In corridors and hallways with a maximum width of 3 m, the distance be-
tween two smoke detectors must not exceed 15 m. The distance to the front
side of the corridor must not exceed 7.5 m.
Straight corridor or hallway
Rectangular corridor or hallway
In large corridors and hallways
In corner areas
Wall
W
all
7.5 m
W
all
W
all