The smoke detector monitors an area of 60 m² with a ceiling height of 6 m
at most.
It has to be mounted on the ceiling in the middle of the room as far as this
is possible. A distance of at least 0.5 m has to be kept to all ceiling fitments
and to the walls according to DIN 14676 (German standard). Clocked power
supplies such as energy-saving lamps, transformers etc. are also considered
as fitments. If the detector is mounted in an attic, it has to be mounted at a
distance of
■
0.2 m - 0.5 m from the top with a roof slope
of up to 20°
. The detector
can be mounted laterally offset and directly onto the ceiling/the roof.
■
0.2 m - 0.5 m horizontally with a roof slope of
more than 20°
.
Dachneigung < = 20 °
0,2 m bis 0,5 m
Dachneigung > 20 °
0.2 m to 0,5 m
Roof slope < = 20°
Roof slope > 20°
Smoke detectors must not be used outdoors.