background image

9

196349 rev 1

EN

8. Extended usage information

8.1  Temperature control (OPTION)

The dryer is equipped with an automatic temperature 
control. This enables optimum drying/curing results 
within the shortest possible time.
The properties when the temperature control is on are:
a. minutes
b. temperature increase/minute
c. max allowed temperature
The temperature control (pyrometer) measures the 
average temperature over a surface. The laser pointer 
indicates where the distance check is made. This pointer 
is close to being in the centre of the temperature mea-
surement also.
In settings mode, the short and long limit for a “correct” 
distance measurement can be adjusted. Default correct 
distance is between 55 and 65 cm.

Note!

 The temperature is measured as an average of the 

measured surface (default diameter value 30 cm, other 
optics are available). Make sure to have the measur-
ing surface placed correctly. Make sure that you don´t 
measure the temperature on glass, tyres or outside the 
object. Otherwise, the result between the programmed 
temperature values and actual values may differ. This 
may lead to unsatisfactory results and if the process 
alarm is activated it will stop the drying/curing.
With the temperature control deactivated, the program 
properties are:
a. minutes
b. percent power of max possible
The program settings with or without the temperature 
control activated are working independently of each 
other.

8.2  Process alarms (OPTION)

To notice temperature deviations, the dryer is equipped 
with a process alarm. If the difference between the 
current temperature and the requested temperature is 
more than 30ºC (adjustable, see 9.4.28), the message 
“Warning! Process error” appears in the display and the 
dryer switches off automatically. This warning has to be 
acknowledged by pressing 

enter

. By doing this, the pro-

gram is terminated. In case of process alarm, check if the 
temperature measuring device (pyrometer) is aligned 
correctly on the surface to be dried and that it is not 
registering unwanted material temperatures.

Attention!

 The process alarm function is not activated 

when dryer is delivered.
Please see chapter 9.4.3 for activating.

8.3  External start and stop

There is an input in this SingleHeater Control Unit to 
enable a remote start and stop of the drying process. 
This function can be integrated in the overhead process. 
When the remote start contact is closed, the drying 
process will automatically start according to the pre-set 
program (1-15). It will then stop when the remote start 
contact is open. See electrical drawings chapter 12.

9. Settings Mode

9.1  Log In

To enter the settings mode you first have to ”log in”. Press 
both arrow keys as you turn the main switch on. The 
display will ask you for a PIN code.

9.2  PIN code

Use the arrow keys to fill in the correct digit. Press 

enter

 

to confirm and edit the second, third, and fourth digit of 
the code.
No code is required for basic settings, just press 

OK

 

for the default code of 0000. To change this code, read 
chapter 9.4.6.

Advanced PIN code 

 

  

5780 

Used for program adjustments and advanced settings. To 
change this code, read chapter 9.4.14.

Attention! 

An entered PIN code is valid globally in the 

software until the main switch is turned off, i.e. if you 
enter advanced settings mode and then exit to program 
mode. The program editing will still be editable until the 
main power is turned off.

9.3  Navigation

To adjust a setting, press 

edit

. To go back from edit mode 

to settings mode without saving, press 

cancel

Note! 

If you press 

exit

 from settings mode you will be re-

directed to program mode.  You will then need to repeat 
from step 9.1 Log In to enter 9.4 Settings again.

Use 

arrow keys 

to 

change language and 

select

 to confirm. 

Use the 

arrow keys

 

to scroll through the 
settings, see table in 
chapter 8.4.

Press 

exit

 

and you will 
be directed 
to “program 
mode”.

Edit 

mode

Summary of Contents for IRT System Series

Page 1: ...196349 rev 1 Hedson Technologies AB 2018 IRT Dryer Siemens Leading Edge Protection EN Operation Manual original language...

Page 2: ...wner 5 5 Assembly instruction 5 6 Basic instruction for operation 5 7 Program mode 8 8 Extended usage information 9 9 Settings mode 9 10 Maintenance and Service 12 11 Spare parts 14 12 Safety inspecti...

Page 3: ...ounted on the lifting platform 1 Safety instructions 1 1 Operator s duty of care The IRT Siemens Leading Edge Protection Dryer is designed and built after a hazard assessment was con sidered and follo...

Page 4: ...king under the raised working platform and during its lifting and lowering movements is not permitted 3 Product description The IRT Siemens Leading Edge Protection Dryer is a maneuverable infrared dry...

Page 5: ...ir only A filter regulator must only be installed in the air supply line air filter and water separator 6 Basic instruction for operation Move the dryer to the site where you want to use it This can o...

Page 6: ...amps Control panel 1 The lights turn green when the correct distance obtained between IR lamps and object This distance must be checked before the IR lights turned on During operation with IR lamps th...

Page 7: ...ered This is normally not a part of the everyday usage To enter the settings mode press both arrow keys when you turn the main switch to position 1 Read chapter 9 for more information 6 8 Program inte...

Page 8: ...is finished If this happens check the cooling system of the con trol unit fan filter or ambient temperature 3 Paint Temperature Alarm Also called Process alarm see 8 2 Option if pyrometer is used 4 Fi...

Page 9: ...ram is terminated In case of process alarm check if the temperature measuring device pyrometer is aligned correctly on the surface to be dried and that it is not registering unwanted material temperat...

Page 10: ...o select no yes Press select to confirm 9 4 6 7 Basic PIN Code You can change the PIN code to prevent unauthor ized access to the basic setting as described in table in chapter 9 4 To do this use the...

Page 11: ...t 4 Cassette IR Test The IR cassette lamps output I light up Check that all the IR lamps are lit For safety reasons this test is limited to 10 seconds Press enter or next to continue Test 5 Ventilator...

Page 12: ...uitably trained personnel Do not use running water or flammable liquids for clean ing Abide by the following points to ensure a long service life and continuous operation of the dryer Only original sp...

Page 13: ...round the lamp until the fit ting is completed 1 Loosen the mounting screws on both end cov ers 2 Loosen both lamp end protections 3 Pull the protection out of the slide The screws for the lamp holder...

Page 14: ...st environmental pro tection facility for recycling 11 Spare parts The following spare parts are the most common ones for the SingleHeater IR units Part Part nr 1 Fan 202024 2 Filter 103055 3 IR lamp...

Page 15: ...s to the zero position when released Fall arrester function Emergency release status Air bellows status Supporting structure status Function test Lifting lowering Function test Lifting lowering with l...

Page 16: ...lowing standard s or other normative document s EN 61000 6 4 Electromagnetic Compatibility Generic Emission Standard EN 61000 6 3 Electromagnetic Compatibility Generic Immunity Standard EN 60204 1 Saf...

Page 17: ...appendix 1 761 054_PNTS 77 Electrical diagram for IRT Siemens Leading Edge Protection Dryer equipment is found in the appendix 2 15 Weights and Dimensions The overall weight is 665 kg Dimensions as b...

Page 18: ...sette tripped Check fans filters hoses and ambient tempera ture Reset by pressing the temp switch button Lifting malfunction Maintenance unit manometer without mains pressure Ensure the mains pressure...

Page 19: ...70 196349 rev 1...

Page 20: ...53 42 00 Telefax 46 0 40 43 29 01 www hedson com HEDSON TECHNOLOGIES AB Box 1530 SE 462 28 V nersborg Tel 46 0 40 53 42 00 Telefax 46 0 521 669 09 www hedson com Hedson Technologies 2017 The manufact...

Reviews: