background image

9

7.0 FAULT FINDING

The SuperChill unit should give trouble free operation, however should a problem 
occur, the tables below should enable most faults to be identified with ease.
Fault finding should be carried out by a competent person and any replacement 
parts used should be authorised Heatrae spare parts.

SYMPTOM

POSSIBLE CAUSE

ACTION

The compressor 

will not start

1. No power to unit

1.  Check  the  power  supply  is  not  faulty  and  is 

swithced on

2. Thermostat set to the OFF or minimum 

cooling position

2. Turn thermostat to ON and adjust to cooler 

temperature

3. Thermostat fault

3. Replace thermostat

4. Wiring fault

4. Check all wireing connections are secure and 

correctly made (refer to Wiring Diagram page 5)

5. Compressor fault

5. Replace compressor

Water is ice cold 

but operates 

excessively

1. Poor ventilation

1. Ensure the unit is 60-70mm from the wall and 

ventillation slots are clean and unobstructed

2.  The  condensor  fins  are  dirty  or  airflow 

over condensor is imparied

2. Clean the condensor (see Section 6.2)

3.  Thermostat  set  to  maximum  cooling 

position

3. Adjust thermostat to a less cool temperature

4. Faulty thermostat

Replace thermostat

5. Thermostat sensing probe not inserted 

into the cold water tank correctly

5.  Ensure  thermostat  sensing  probe  is  pushed 

fully into pocket in tank

6. High ambient temperatire (>45°C)

6 . At high ambient temperatures it is normal for 

the unit to work continuosly

Compressor 

works 

continuosly, but 

water is not cold

1. Gas leak from the cooling system

1. The remaining gas must be emptied and the 

leak  must  be  sealed.  The  unit  should  then  be 

recharged with the correct quality of gas (refer 

to Technical Data on page 2 or data plate on the 

appliance) NOTE: This action must only be done 

by a qualified person.

2. Faulty compressor

2. Replace compressor

3. Coooling fan does not work

3. Replace cooling fan

4. Water low in ice bank

4. Top-up or replace ice bank (see page 6)

Unit works 

excessibely, but 

water is not cold 

enough

1.  Cold  reservoir  is  frequently  exhausted 

by heary usage

1. The units cold water output is beeing exceeded 

(see Technical Data page 5), Consider a larger unit 

or installing another nearby

Water is cold, 

but unit is 

excessibely noisy

1. Pipe vibration

1. Check that water pipes are not vibrating against 

other  parts  of  the  unit,  adjust  their  position  if 

necessary

NOTE: This unit contains a copressor and the fan so some noise will be normal when these 

are in operation.

Poor water flow

1. Low water pressure

1. Ensure water pressure is a minimum of 1 bar

2. Water filter clogged

2. Check and , if necessary, change water filter 

cartridge

3. Thermostat sensor not inserted into the 

housing of the cold water tank causing water 

in tank to freeze

3.  Switch  off  unit  and  allow  to  thaw.  Insert 

thermostat  sensor  correctly  into  housing  in 

tank.

Summary of Contents for SUPERCHILL 30B

Page 1: ...SUPERCHILL 30B Fitting Instructions and User Guide...

Page 2: ...n or instruction concerning the use of the appliance by a person responsible for their safety Children should be supervised to ensure they do not play with the SuperChill unit The SuperChill unit does...

Page 3: ...nsor assembly should be periodically cleaned to prevent a build up of dust or dirt on the cooling fins 1 5 The chiller must be installed vertically on a level surface 1 6 If you have purchased an inli...

Page 4: ...iller must be installed inside a building DO NOT install outside or in a position where it could be influenced by inclement weather conditions 2 6 DO NOT install where the unit may be exposed to extre...

Page 5: ...must be allowed for removal and replacement of the filter cartridge Connection of the water supply to the chiller and filter assembly is by means of an 8mm outside diameter flexible WRAS listed plast...

Page 6: ...es to flush through the filter internal pipes tank and fittings of any air dust or debris that may have accumulated during transit or installation 5 6 Check that the filler spout is positioned at an a...

Page 7: ...umstances evaporation salts may have accumulated around the outlet points This should be cleaned with a proprietary scale remover approved for sanitary ware Ensure all traces of the cleaner are remove...

Page 8: ...ia a small pump 6 3 4 Start the pump and operate the outlet to allow the disinfecting solution to enter the chiller Allow approximately 4 litres of solution to enter the chiller to ensure the chilling...

Page 9: ...tank 6 High ambient temperatire 45 C 6 At high ambient temperatures it is normal for the unit to work continuosly Compressor works continuosly but water is not cold 1 Gas leak from the cooling system...

Page 10: ...the water chiller is not in use for long periods during the winter months set the thermostat to a higher position 9 2 If the SuperChill water chiller is fitted with an in line filter that will remove...

Page 11: ...tions The unit has been used only for chilling potable water The unit is not 4 guaranteed against damage by frost or due to the build up of scale The guarantee does not cover the filter 10 0 ENVIRONME...

Page 12: ...Mail sales ewh co uk SPD Units 9 10 Hexagon Business Centre Springfield Road Hayes Middlesex UB40 0TY Tel 020 8606 3567 Parts Center Tel 0845 2709800 www partscenter co uk Newey Eyre Specialist Produc...

Reviews: