Heatilator • Caliber CD Series • 4040-263 Rev M • 06/08
27
Figure 7.9
2. Top Vent - Vertical Termination - (continued)
Three Elbows
12 ft (3.66 m) min.
60 ft (18.29 m) max.
Maximum horizontal run is
100% of vertical, but cannot
exceed 26 ft (7.92 m)
Note:
If installing a vertical vent/
termination off the top of the appli-
ance, the vertical termination baf
fl
e
should be used.