21
Please keep these instructions for future reference.
Equipment assembly and Wiring is required before using this Guide.
For assembly please consult Intelligen Assebly and Wiring Guide.
PRIOR ASSEMBLY NEEDED
IMPORTANT!
This Quick Start Guide is
only for Intelligen Series XXKSJFS Model.
IMPORTANT!
Since product improvement is a continuing effort, we reserve the
right to make changes in specifications without notice.
Normal Business Hours – 8:00 AM – 8:00 PM EDT
(800) 321-1881
After Hours (after 5:00 PM EDT, weekends and holidays)
(877) 482-7238
heatcraft.com/intelligen/support
US. Customer Service
Normal Business Hours – 8:00 AM – 8:00 PM EDT
(800) 321-1881
After Hours (after 5:00 PM EDT, weekends and holidays)
(877) 482-7238
heatcraft.com/intelligen/support
Canada Customer Service
QUICK START GUIDE
INTELLIGEN 00049DFS
MARCH 2018*
*REPLACES JANUARY 2018
PART NO. 099483
Modbus Register Mapping
TO READ/WRITE PARAMETERS OVER EXTERNAL MODBUS (cont.)
Field Name
Data Address
Type
Quantity of Registers
Decoding Method
RO/RW?
Force Defrost
0x403D
Integer
1
Writing ‘1’ would force
defrost
WO
System Alarms
0x403E
Integer
2
Refer System Alarm
Table
RO
Enable
(n * C)
Integer
1
0 – Disabled; 1 –
Enabled . If Enabled is
0, below parameters
should be ignored for
that unit
RO
Unit Address
(n *
C) + 1
Integer
1
RO
Unit Type
0x40 + (n * C)
+ 2
Integer
1
RO
EV Superheat Setpoint
(n*
C) + 3
Signed Integer
1
Real number multiplied
by 10
RW
Unit Alarms/Errors
(n *
C) + 4
4
Refer Unit Alarms Table
RO
Short Unit Name
(n *
C) + 8
Strings
2
ASCII characters sent in
data bytes
RO
TABLE 2
Field Name
Data Address
Type
Quantity of Registers
Decoding Method
RO/RW?
LED Bar Enable
0x5000
Integer
1
No-0, Yes-1
RW
External Modbus Address
0x5001
Integer
1
0 to 246
RW*
External BACnet Address
0x5002
Integer
1
0 to 127
RO
CU Wired Address
0x5007
Integer
1
RCB Address.
RW*
BACnet Baudrate
0x5008
Integer
1
0-9600, 2-38400
RO
Enter Service Mode
0x5009
Integer
1
Exit Service Mode-0,
Enter Service Mode-1
RW
Primary EV Address
0x500A
Integer
1
RCB Address –- 0 - 7th
bit.
Prim/aux - 8th bit.
Primary – 0
Auxiliary – 1
RW
Note: * Refer Read Write Special Cases section. n is an index into number of unit records ranging from [0 to N-1] EV units where max N = 8.
* Refer to Read Write Special Cases section