17
Please keep these instructions for future reference.
Equipment assembly and Wiring is required before using this Guide.
For assembly please consult Intelligen Assebly and Wiring Guide.
PRIOR ASSEMBLY NEEDED
IMPORTANT!
This Quick Start Guide is
only for Intelligen Series XXKSJFS Model.
IMPORTANT!
Since product improvement is a continuing effort, we reserve the
right to make changes in specifications without notice.
Normal Business Hours – 8:00 AM – 8:00 PM EDT
(800) 321-1881
After Hours (after 5:00 PM EDT, weekends and holidays)
(877) 482-7238
heatcraft.com/intelligen/support
US. Customer Service
Normal Business Hours – 8:00 AM – 8:00 PM EDT
(800) 321-1881
After Hours (after 5:00 PM EDT, weekends and holidays)
(877) 482-7238
heatcraft.com/intelligen/support
Canada Customer Service
QUICK START GUIDE
INTELLIGEN 00049DFS
MARCH 2018*
*REPLACES JANUARY 2018
PART NO. 099483
S.No
Property Name
Property ID
Type
RW/RO/WO
30
Error 18 evaporator auxiliary temperature sensor
588
Boolean
RO
31
Error 19 replace battery
589
Boolean
RO
32
Error 20 log disrupted
590
Boolean
RO
33
Error 22 RCBUI failure
592
Boolean
RO
34
Alarm input fault
563
Boolean
RO
35
Object Installed
595
Boolean
RO
36
Error 26 EV Connection Lost
622
Boolean
RO
37
EV Length of Last Defrost
623
Integer
RO
38
EV RCB Control Voltage
624
Real
RO
BACnet Mapping – “Unit Local Settings Object Type”
* Refer to Read Write Special Cases section
ERRORS FOR READ/WRITE PROPERTIES:
- ERROR_CODE_UNKNOWN_PROPERTY– If the property address does not exist in the system.
- ERROR_CODE_WRITE_ACCESS_DENIED – Invalid Value (i.e. within the range some intermediate values are not valid).
- ERROR_CODE_VALUE_OUT_OF_RANGE - If the values are not in the specified range.