Please keep these instructions for future reference.
Equipment assembly and Wiring is required before using this Guide.
For assembly please consult Intelligen Assebly and Wiring Guide.
PRIOR ASSEMBLY NEEDED
IMPORTANT!
This Quick Start Guide is
only for Intelligen Series XXKSJFS Model.
IMPORTANT!
Since product improvement is a continuing effort, we reserve the
right to make changes in specifications without notice.
Normal Business Hours – 8:00 AM – 8:00 PM EDT
(800) 321-1881
After Hours (after 5:00 PM EDT, weekends and holidays)
(877) 482-7238
heatcraft.com/intelligen/support
US. Customer Service
Normal Business Hours – 8:00 AM – 8:00 PM EDT
(800) 321-1881
After Hours (after 5:00 PM EDT, weekends and holidays)
(877) 482-7238
heatcraft.com/intelligen/support
Canada Customer Service
QUICK START GUIDE
INTELLIGEN 00049DFS
MARCH 2018*
*REPLACES JANUARY 2018
PART NO. 099483
iIC- intelliGen INTEGRATION CARD
Installation
• If an iWC (webserver card) is used in the system, be sure to connect the iIC (integration card) to the
same evaporator board. If no iWC is present in the system, the iIC may be connected to ANY
evaporator board.
• While system is powered down, align & insert iIC's pins into iRC board’s plug, insert card into board.
• Secure with mounting screws. For proper mounting, use #6-32x1 inch stainless machine screws.
• Wiring to the pluggable terminal block must be in accordance to the wiring prescribed by your
BAS connection protocol. RS-485, 22 or 24 AWG shielded twisted pair cables, such as Belden 9841
or equivalent, is recommended.
• iIC can be used with an existing building management system.
Configuration and Initial Setup
PROTOCOLS SUPPORTED
• BACnet MS/TP
• Modbus (RTU)
OPTION 1: CONFIGURE OVER WEB PAGE (IF IWC IS IN USE)
• Confirm iIC is installed by checking the status on the intelliGen Dashboard
• In
GENERAL SETTINGS
tab, under the
ADVANCED
section, select the protocol to be used.
Either
MODBUS
or
BACnet
System Name