background image

Heat & Glo  •  TIARAI-BK-IPI, TIARAI-BR-IPI, TIARAI-CES-IPI Installation Manual  •  2342-980_R8  •  11/14

45

B.  wiring Requirements

Intellifire

TM

 Plus Ignition System wiring

•  Plug the cord from the appliance junction box to 110-120 

Vac for proper operation of the appliance.

WARNING! Risk of Shock or Explosion! DO NOT

 wire 

IPI controlled appliance junction box to a switched circuit. 

Incorrect wiring will override IPI safety lockout.

•  Refer to Figure 8.1, IPI Wiring diagram.
•  this appliance is equipped with an IntelliFire™

 

 Plus control 

valve which operates on a 6 volt/1.5 aMP system.

•  Plug the 6 volt transformer plug into the appliance junction 

box to supply power to the unit oR install 4 aa  cell batteries 

(not included) into the battery pack before use.

NOTICE: 

Batteries should only be used as a power source 

in the event of an emergency power outage. Batteries should 

not be used as a primary long-term power source. Battery 

polarity must be correct when installing batteries. 

do not store batteries in the battery pack when the 

appliance is powered by the 6 volt transformer connected to 

permanent electrical service.

Figure 8.1 IPI wiring Diagram

TO JUNCTION 

BOX (110V)

MODULE

FLAME 

SENSE

IGNITER

RC100                      RC200                   RC300

(OPTIONAL WALL CONTROLS)

GROUND

ORANGE

(PILOT)

GREEN

(MAIN)

BROWN

BLACK

RED

BATTERY PACK

6V DC 

FLAME 

MODULATION

BLACK

BLACK

RED

BROWN

Summary of Contents for TIARAI-BK-IPI

Page 1: ...censed plumber or gas fitter See Table of Contents for location of additional Commonwealth of Massachusetts requirements WARNING If the information in these instructions is not followed exactly a fire or explosion may result causing property damage personal injury or death DO NOT store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance What to do i...

Page 2: ...ion Floor Protection 8 4 Termination Location and Vent Information A Vent Termination Minimum Clearances 9 B Chimney Diagram 10 C Approved Pipe 11 D Use of Elbows 12 E Measuring Standards 12 F Venting Guidelines for Horizontal Runs 13 G Vent Diagrams 13 5 Vent Clearances and Framing A Pipe Clearances to Combustibles 30 B Wall Penetration Framing Firestops 30 C Ceiling Firestop Floor Penetration Fr...

Page 3: ...________________ Electrical Section 8 Pg 44 47 Unswitched power 110 120 VAC provided for the appliance ___________________________ Switch wires properly installed ___________________________ Gas Section 9 Pg 48 49 Appliance con guration matches fuel type ___________________________ Was a conversion performed ___________________________ Leak check performed and inlet outlet pressure veri ed _______...

Page 4: ...2000 feet In CANADA Input ratings are certified without a reduction of input rate for elevations up to 4500 feet 1370 m above sea level Please consult provincial and or local authorities having jurisdiction for installations at elevations above 4500 feet 1370 m Check with your local gas utility to determine proper orifice size E Non Combustible Materials Specification Material which will not ignit...

Page 5: ...ntally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 in in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS Note The following requirements reference various Massachusetts and national codes not contained in this document Inspection The state or local gas inspector of the side wall horizontally vented gas fueled equipment sh...

Page 6: ...ols and Supplies Needed Before beginning the installation be sure that the following tools and building supplies are available Tape measure Framing material Pliers Hammer Phillips screwdriver Manometer Gloves Framing square Voltmeter Electric drill and bits 1 4 in Plumb line Safety glasses Level Reciprocating saw Flat blade screwdriver Non corrosive leak check solution 1 2 3 4 in length 6 or 8 Sel...

Page 7: ...mensions are actual appliance dimensions Use for reference only Figure 3 1 Appliance Dimensions Location Inches Millimeter Location Inches Millimeter A 23 1 4 590 D 20 1 4 514 B 9 3 8 237 E 11 3 4 298 C 27 686 F 20 506 NOTE Diagrams show gas appliance equipped without optional Blower Part GFK 160A FRONT SIDE A B C D E F BACK GAS LINE ELECTRICAL CORD ...

Page 8: ...nce Locations Model A B C D E F G H Top of pipe Side of pipe Inside Outside corner wall vent TIARAI IPI Inches 8 1 2 1 4 3 8 54 36 40 1 4 27 3 1 9 Millimeters 216 6 10 1372 914 1022 686 76 25 229 A B F E A A measurement is from stove top not side G H D C C A G A C Hearth Extension Floor Protection CAUTION Risk of Fire or Injury Install appliance on a stable level platform or floor strong enough to...

Page 9: ... TO LOWEST DISCHARGE OPENING 4 Termination Location and Vent Information Fire Risk Maintain vent clearance to combustibles as specified DO NOT pack air space with insulation or other materials Failure to keep insulation or other materials away from vent pipe may cause overheating and fire Figure 4 2 Staggered Termination Caps Gas Wood or Fuel Oil Termination Cap B Gas Termination Cap A If using de...

Page 10: ...NAL IS NOT PERMITTED O N P R Q Electrical Service V K V K V L C V QMIN RMAX 1 cap 3 feet 2 x Q ACTUAL 2 caps 6 feet 1 x Q ACTUAL 3 caps 9 feet 2 3 x Q ACTUAL 4 caps 12 feet 1 2 x Q ACTUAL QMIN termination caps x 3 RMAX 2 termination caps x QACTUAL Covered Alcove Applications Spaces open only on one side and with an overhang N 6 inches non vinyl sidewalls 12 inches vinyl sidewalls O 18 inches non v...

Page 11: ...S This product is approved to be vented either horizontally through the side wall or vertically through the roof You may vent through a Class A or masonry chimney if an approved adapter is used This appliance is a direct vent heater All combustion air must come directly from the outside of the building The vent pipe for this unit consists of an inner and an outer pipe The inner pipe carries the ap...

Page 12: ... Type X Y Inches Millimeters Inches Millimeters SLP 5 127 11 3 4 298 SLP Pipe Effective Length Rise Run Inches Millimeters Inches Millimeters SLP4 4 102 2 3 4 70 SLP6 6 152 4 1 4 108 SLP12 12 305 8 1 2 216 SLP24 24 610 17 432 SLP36 36 914 25 1 2 648 SLP48 48 1219 34 864 SLP6A 3 to 6 76 to 152 2 1 8 4 1 4 54 108 SLP12A 3 to 12 76 to 305 2 1 8 8 1 2 54 216 Figure 4 5 Vertical and Horizontal Offset f...

Page 13: ...Top Vent Horizontal Termination Two 45º Elbows Installation requirements to replace the first 90º elbow with two 45º elbows 4 ft min 1 22 m Figure 4 7 Figure 4 6 F Venting Guidelines for Horizontal Runs C L Snorkel Kit Max Horizontal Run Rear Vent No Rise 14 in 356 mm Snorkel kit and derating orifice must be used See Figure 4 6 Max Horizontal Run 14 ft 4 3 m when vertical rise is 10 ft 3m Max Hori...

Page 14: ...n V1 H1 Maximum 1 ft 305 mm 14 in 356 mm 2 ft 610 mm 9 ft 2 7 m 4 ft 1 2 m 10 ft 3 in 3 1 m 6 ft 1 8 m 11 ft 6 in 3 5 m 8 ft 2 4m 12 ft 9 in 3 9 m 10 ft 3 0 m 14 ft 4 3 m 12 ft 3 7 m 13 ft 2 in 4 0 m 16 ft 4 9 m 11 ft 3 in 3 4 m 20 ft 6 1 m 9 ft 4 in 2 7 m 24 ft 7 3 m 7 ft 6 in 2 3 m 28 ft 8 5 m 5 ft 7 in 1 7 m 30 ft 9 1 m 4 ft 7 in 1 4 m H1 V1 ...

Page 15: ...Max Horizontal V1 Minimum H1 H2 Maximum 2 ft 610 mm 6 ft 1 8 m 4 ft 1 2 m 7 ft 3 in 2 2 m 6 ft 1 8 m 8 ft 6 in 2 6 m 8 ft 2 4 m 9 ft 9 in 3 0 m 10 ft 3 1 m 11 ft 3 4 m 12 ft 3 7 m 10 ft 2 in 3 1 m 16 ft 4 9 m 8 ft 3 in 2 5 m 20 ft 6 1 m 6 ft 4 in 1 9 m 24 ft 7 3 m 4 ft 6 in 1 4 m 28 ft 8 5 m 2 ft 7 in 787 mm 30 ft 9 1 m 1 ft 9 in 533 mm Figure 4 9 ...

Page 16: ...ed Three Elbows 3 Elbows to Max Horizontal V1 Minimum H1 H2 Maximum 2 ft 610 mm 3 ft 914 mm 4 ft 1 2 m 4 ft 3 in 1 3 m 6 ft 1 8 m 5 ft 6 in 1 7 m 8 ft 2 4 m 6 ft 9 in 2 1 m 10 ft 3 1 m 8 ft 2 4 m 12 ft 3 7 m 7 ft 2 in 2 2 m 16 ft 4 9 m 5 ft 3 in 1 6 m 20 ft 6 1 m 3 ft 4 in 1 0 m 24 ft 7 3 m 1 ft 6 in 457 mm 28 ft 8 5 m 11 in 279 mm 30 ft 9 1 m 11 in 279 mm ...

Page 17: ...Heat Glo TIARAI BK IPI TIARAI BR IPI TIARAI CES IPI Installation Manual 2342 980_R8 11 14 17 Top Vent Vertical Termination No Elbow Figure 4 11 V1 V1 30 ft Max 9 1 m V1 6 ft Min 1 8 m ...

Page 18: ... 4 in 8 3 m 6 ft 1 8 m 4 ft 1 2 m 24 ft 8 in 7 5 m 7 ft 3 in 2 2 m 6 ft 1 8 m 22 ft 6 7 m 8 ft 6 in 2 6 m 8 ft 2 4 m 19 ft 4 in 5 9 m 9 ft 9 in 3 0 m 10 ft 3 1 m 16 ft 8 in 5 1 m 11 ft 3 4 m 12 ft 3 7 m 18 ft 8 in 5 7 m 10 ft 2 in 3 1 m 16 ft 4 9 m 22 ft 8 in 6 9 m 8 ft 3 in 2 5 m 20 ft 6 1 m 26 ft 8 in 8 1 m 6 ft 4 in 1 9 m 24 ft 7 3 m 30 ft 9 1 m 4 ft 6 in 1 4 m 28 ft 8 5 m 34 ft 9 1 m 2 ft 7 in...

Page 19: ... Horizontal V1 Minimum V1 V2 Maximum H1 H2 Maximum 2 ft 610 mm 30 ft 9 1 m 6 ft 1 8 m 4 ft 1 2 m 30 ft 9 1 m 7 ft 3 in 2 2 m 6 ft 1 8 m 28 ft 2 in 8 6 m 8ft 6 in 2 6 m 8 ft 2 4 m 25 ft 6 in 7 8 m 9 ft 9 in 3 0 m 10 ft 3 1 m 21 ft 6 4 m 11 ft 3 4 m 12 ft 3 7 m 24 ft 8 in 7 5 m 11 2 m 2 2 m 16 ft 4 9 m 29 ft 8 8 m 5 ft 3 in 1 6 m 20 ft 6 1 m 30 ft 9 1 m 3 ft 4 in 1 0 m 24 ft 7 3 m 30 ft 9 1 m 1 ft 6...

Page 20: ...s application and is included in the Rear Vent Kit Note A derating orifice is required with this application and is included in the Rear Vent Kit Note All horizontal vent pipe runs must have 1 4 inch rise per foot Note All horizontal vent pipe runs must have 1 4 inch rise per foot NOTICE An SLK SNKD is required for this vent configuration NOTICE An SLK SNKD is required for this vent configuration ...

Page 21: ... mm 6 ft 1 8 m 6 in 152 mm 8 ft 6 in 2 6 m 14 in 357 mm 8 ft 2 4 m 6 in 152 mm 9 ft 9 in 3 0 m 14 in 357 mm 10 ft 3 1 m 6 in 152 mm 11 ft 3 4 m 14 in 357 mm 12 ft 3 7 m 6 in 152 mm 10 ft 2 in 3 1 m 14 in 357 mm 16 ft 4 9 m 6 in 152 mm 8 ft 3 in 2 5 m 14 in 357 mm 20 ft 6 1 m 6 in 152 mm 6 ft 4 in 1 9 m 14 in 357 mm 24 ft 7 3 m 6 in 152 mm 4 ft 6 in 1 4 m 14 in 357 mm 28 ft 8 5 m 6 in 152 mm 2 ft 7...

Page 22: ...mm 14 in 357 mm 4 ft 3 in 1 3 m 6 ft 1 8 m 6 in 152 mm 14 in 357 mm 5 ft 6 in 1 7 m 8 ft 2 4 m 6 in 152 mm 14 in 357 mm 6 ft 9 in 2 1 m 10 ft 3 1 m 6 in 152 mm 14 in 357 mm 8 ft 2 4 m 12 ft 3 7 m 6 in 152 mm 14 in 357 mm 7 ft 2 in 2 2 m 16 ft 4 9 m 6 in 152 mm 14 in 357 mm 5 ft 3 in 1 6 m 20 ft 6 1 m 6 in 152 mm 14 in 357 mm 3 ft 4 in 1 0 m 24 ft 7 3 m 6 in 152 mm 14 in 357 mm 1 ft 6 in 457 mm Not...

Page 23: ...al 2342 980_R8 11 14 23 Rear Vent Vertical Termination Figure 4 18 H1 Minimum H1 Maximum V1 Minimum V1 Maximum 6 in 152 mm 14 in 357 mm 6 ft 1 8 m 40 ft 12 2 m H1 V1 Note A derating orifice is required with this application and is included in the Rear Vent Kit One Elbow ...

Page 24: ...9 5 m 6 ft 1 8 m 6 in 152 mm 14 in 357 mm 5 ft 6 in 1 7 m 28 ft 2 in 8 6 m 8 ft 2 4 m 6 in 152 mm 14 in 357 mm 6 ft 9 in 2 1 m 25 ft 6 in 7 8 m 10 ft 3 1 m 6 in 152 mm 14 in 357 mm 8 ft 2 4 m 23 ft 7 0 m 12 ft 3 7 m 6 in 152 mm 14 in 357 mm 7 ft 2 in 2 2 m 24 ft 8 in 7 5 m 16 ft 4 9 m 6 in 152 mm 14 in 357 mm 5 ft 3 in 1 6 m 28 ft 8 in 8 7 m 20 ft 6 1 m 6 in 152 mm 14 in 357 mm 3 ft 4 in 1 0 m 32 ...

Page 25: ...t the flex pipe to the retro connector and attach with sheet metal screws 6 Push the flex pipe back up into the ceiling support box center the retro connector and attach it to the support box with sheet metal screws 7 The connection between the appliance and the retro connector may be completed with sections of direct vent pipe Top Adapter Sheet Metal Screws Flex Pipe Figure 4 21 Figure 4 20 1 Rem...

Page 26: ...x Liner Chimney Liner Termination Cap Co Axial to Co Linear Connector 30 ft 9m of 3 in 76mm Flex Liner Exhaust Section 4 ft 1m of 3 in 76mm Flex Liner Air Intake Section The chimney must be sealed from the 4 ft 1m section to termination using a smoke shelf or a flue restrictor The seal should be a minimum of 6 in 152mm below the end of the 4 ft 1m Air Intake section This section of the chimney mus...

Page 27: ...vel of the opening Add the distance from the center of the chimney out through the wall Cut a piece of 4 in 102mm flex to this length extended to its nominal length Be sure to leave 2 3 in 51 76mm of flex above the existing chimney to allow for connection to the termination kit 5 Connect the flex liner to the top adapter using three sheet metal screws See Figure 4 21 6 Feed the flex liner through ...

Page 28: ...ro Connector Wall Thimble Cover Figure 4 27 8 Secure the top adapter to the flashing Use three sheet metal screws through the side of the top adapter into the flange on the flashing See Figure 4 28 Twist lock the high wind termination cap on to the top adapter Flex Liner Flex Coupler Sheet Metal Screws Figure 4 30 Figure 4 29 10 Slide wall thimble cover over retro connector and secure with masonry...

Page 29: ...cal building codes Figure 4 31 Coaxial Colinear Appliance Connector WARNING Risk of Fire Coaxial to colinear venting configuration may only be used in existing non combustible chimney Installation in any other venting application could cause fire WARNING Risk of Fire Explosion or Asphyxiation Do NOT connect this gas appliance to a chimney flue serving a separate solid fuel or gas burning appliance...

Page 30: ... an interior wall A minimum 1 1 2 in 38 mm overlap of attached heat shields must be maintained See Section 7 F for information for regarding the installation of a horizontal termination cap Non Combustible Wall Penetration If the hole being penetrated is surrounded by non combustible materials such as concrete a hole with diameter one inch greater than the pipe is acceptable Whenever a non combust...

Page 31: ... from the pipe to prevent overheating D Install Attic Insulation Shield WARNING Fire Risk DO NOT allow loose materials or insulation to touch vent Hearth Home Technologies requires the use of an attic shield The International Fuel Gas Code requires an attic shield constructed of 26 gauge minimum steel that extends at least 2 in 51 mm above insulation Attic insulation shields must meet specified cl...

Page 32: ...P Orifice 55 Tools Required Power drill 1 4 in hex driver bit 3 8 in open end wrench high temperature sealant if required Note TIARAI IPI unit is shown in the photos and drawings in this instruction Instructions apply to both TIARAI IPI and SAPH IPI units Figure 4 4 Locate the knock out on rear of appliance Break the seal on the knock out and discard the knock out Figure 1 1 Remove top grille as h...

Page 33: ...Remove the two screws that attach the pilot to the burner Lift the pilot slightly until it clears the pilot mounting tabs See Figure 13 14 Remove two burner mounting screws from each side of the burner Lift burner up and out of appliance See Figure 13 Note The TIARAI IPI is shown in Figures 9 13 The SAPPHIRE IPI is assembled in a similar manner REMOVE SCREWS 6 Figure 8 Attach inner collar adapter ...

Page 34: ... to the burner shield Figure 14 16 Reinstall burner with four screws 17 On inside of firebox remove plate and gasket on rear of firebox by removing three screws as shown in Figure 14 Discard gasket Replace screws on rear of firebox Remove three screws as shown in Figure 15 Attach plate and new gasket included in kit with three screws 18 Reinstall upper baffle Ensure the upper portion of the baffle...

Page 35: ...aintain air space clearance may cause overheating and fire Figure 8 10 1 Thread Allen bolts through nuts until flush NOTE Two Allen bolts and two nuts are included in the component bag Normally only one is required on the leg not touching the floor Figure 8 12 3 Use a 5 32 in 4mm Allen wrench to adjust legs up and down to desired level Figure 8 11 2 Slide assembled nuts and bolts into slots on leg...

Page 36: ...ted and locked into the preceding component Required Commercial Multi family Multi level exceeding two stories or High Rise Applications For Installation into a commercial multi family multi level exceeding two stories or high rise applications All outer pipe joints must be sealed with high temperature silicone 300º F minimum continuous exposure rating including the slip section that connects dire...

Page 37: ...e Sections NOTICE If slip section is too long the inner and outer flues of the slip section can be cut to the desired length Apply a bead of silicone sealant 300º F minimum continuous exposure rating inside the female outer pipe joint prior to joining sections Only outer pipes are sealed sealing the inner flue is not required All unit collar pipe slip section elbow and cap outer flues shall be sea...

Page 38: ... be supported every 8 ft 2 44 m after the maximum allowed 25 ft 7 62 m of unsupported rise Vertical runs originating off the rear of the appliance or after any elbow must be supported every 8 ft 2 44 m Horizontal runs must be supported every 5 feet 1 52 m Vent supports or plumbers strap spaced 120º apart may be used to support vent sections See Figures 7 5 and 7 6 Wall shield firestops may be used...

Page 39: ...utline of the cathedral ceiling support box on the outside roof Remove shingles or other roof covering as necessary to cut the rectangular hole for the support box Cut the hole 1 8 in 3 mm larger than the support box outline Lower the support box through the hole in the roof until its bottom is at least 2 in 51 mm below the ceiling Figure 7 9 Level the support box both vertically and horizontally ...

Page 40: ...CHARGE OPENING Figure 7 11 Minimum Height From Roof To Lowest Discharge opening NOTICE Failure to properly caulk the roof flashing and pipe seams may permit entry of water Caulk the gap between the roof flashing and the outside diameter of the pipe Caulk the perimeter of the flashing where it contacts the roof surface See Figure 7 15 Caulk the overlap seam of any exposed pipe sections that are loc...

Page 41: ...embled storm collar down the pipe section until it rests on the roof flashing see Figure 7 14 Tighten nut and make sure the collar is tight against the pipe section Caulk around the top of the storm collar See Figure 7 15 Termination Cap 1 of 3 Storm Collar Caulk Screws Figure 7 15 Install Vertical Termination Cap Attach the vertical termination cap by sliding the inner collar of the cap into the ...

Page 42: ... 1 1 2 in 38 mm overlap MUST be maintained Use an extended heat shield if the finished wall thickness is greater than 7 1 4 in 184 mm The extended heat shield may need to be cut to length maintaining sufficient length for a 1 1 2 in 38 mm overlap between heat shields Attach the extended heat shield to either of the existing heat shields using the screws supplied with the extended heat shield Refer...

Page 43: ...the cap base Flash and seal as appropriate for siding material at outside edges of cap When installing a horizontal termination cap follow the cap location guidelines as prescribed by current ANSI Z223 1 and CAN CGA B149 installation codes and refer to Section 6 of this manual CAUTION Risk of Burns Local codes may require installation of a cap shield to prevent anything or anyone from touching the...

Page 44: ...lectrical codes when it is installed in locations such as in bathrooms or near sinks Low voltage and 110 120 VAC voltage cannot be shared within the same wall box WARNING Risk of Shock Plug 3 pronged grounding plug directly into a properly grounded 3 pronged receptacle DO NOT cut or remove grounding prong from plug Accessories Requirements This appliance may be used with a wall switch wall mounted...

Page 45: ...tem Plug the 6 volt transformer plug into the appliance junction box to supply power to the unit OR install 4AA cell batteries not included into the battery pack before use NOTICE Batteries should only be used as a power source in the event of an emergency power outage Batteries should not be used as a primary long term power source Battery polarity must be correct when installing batteries Do not...

Page 46: ...t the switch box connect the black hot wire and red switch leg wire to the wall switch as shown At the appliance connect the black hot white neutral and green ground wires to the junction box as shown Add a 1 4 in insulated female connector to the red switch leg wire route it through the knockout in the face of the junction box and connect to the top fan switch connector 1 4 in male as shown Red S...

Page 47: ...sing with the magnetic strips down staggering the gas line The fan cord should be toward the inside of the appliance Bend tabs upward approximately 45 degrees See Figure 8 3 Figure 8 3 Fan Housing 2 From the front of the appliance plug the blower cord into the junction box receptacle labeled FAN Wrap the extra cord inside the controls area in a manner so that it does not contact the bottom of the ...

Page 48: ...OTICE If the heating value of the gas has been reduced these rules do not apply Check with your local gas utility or authorities having jurisdiction When installing above 2000 feet elevation In the USA Reduce input rate 4 for each 1000 feet above 2000 feet In CANADA Input ratings are certified without a reduction of input rate for elevations up to 4500 feet 1370 m above sea level Please consult pr...

Page 49: ... The air shutter is set fully open at the factory for minimum vertical vent run Adjust air shutter for longer vertical runs See Figure 9 1 Loosen the wing nuts Slide the wing nut to the right to close the air shutter Slide the wing nut to the left to open the air shutter Tighten the wing nuts NOTICE If sooting occurs provide more air by opening the air shutter Figure 9 1 Air Shutter WING NUTS FOR ...

Page 50: ...ifting up If the stove is already installed in a top vented configuration the top casting will need to be lifted slightly to accommodate removal of the front casting See Figure 10 1 Set front casting aside on prepared work surface 2 Release both glass latches at the lower corners of the appliance Remove glass from appliance See Figure 10 2 10 Appliance Setup B Remove the Shipping Materials Remove ...

Page 51: ...ce Log 2 into void on right side of burner Slide log to the left until it contacts the burner topography See Figure 3 Log 3 2342 703 Place Log 3 into void on left side of burner and slide log to the right until it contacts the burner topography See Figure 4 Mineral Wool 050 721 Place dime sized pieces of mineral wool loosely over the burner ports Only place mineral wool on the ports that are locat...

Page 52: ...he gasket to ensure it is undamaged and inspect the glass for cracks chips or scratches DO NOT strike slam or scratch glass DO NOT operate fireplace with glass removed cracked broken or scratched Replace as a complete assembly Reinstall the glass frame by engaging the latches at the bottom corners of the firebox with the glass frame tabs See Figure 10 1 and 10 2 for reference Reinstall front casti...

Page 53: ... mm 9 1 4 in 235 mm SLP90 90 Elbow Effective Height Length SLP PIPE SLP HVS Horizontal Pipe Support 10 7 8 in 276 mm 8 7 8 in 225 mm 1 1 2 in 38 mm SLP FS Ceiling Firestop 8 11 16 in 220 mm 8 11 16 in 220 mm 1 1 2 in 38 mm SLP WS Wall Shield Firestop 12 in 305 mm 12 in 305 mm 5 1 2 in 146 mm Effective Height Length Pipe inches mm SLP4 4 102 SLP6 6 152 SLP12 12 305 SLP24 24 610 SLP36 36 914 SLP48 4...

Page 54: ...is less than 4 in 102 mm the existing heat shields must be field trimmed If wall thickness is greater than 7 1 4 in 184 mm a DVP HSM B will be required Heat Shield Term Cap Minimum Effective Length Maximum Effective Length Trap1 3 1 8 in 4 3 4 in 79 mm 121mm Trap2 5 1 4 in 9 1 4 in 133 mm 235 mm 8 in 203 mm 12 in 305 mm Max Effective Length 14 7 16 in 367 mm 14 7 16 in 367 mm 2 5 16 in 59 mm 3 15 ...

Page 55: ... in 273 mm 10 9 16 in 269 mm 14 in 356 mm SLP CCS BK Cathedral Ceiling Support Box Black 13 in 330 mm 13 in 330 mm 1 5 16 in 34 mm SLP DCF BK Ceiling Firestop Black 12 1 2 in 318 mm 12 in 305 mm SLP TVHW Vertical Termination Cap SLK SNKD Snorkel Termination Cap 13 1 2 in 343 mm 28 1 2 in 724 mm 10 11 16 in 271mm A Vent Components Diagrams continued Figure 11 3 SLP Series Vent Components ...

Page 56: ... Figure 11 4 SLP Series Vent Components A Vent Components Diagrams continued SLP LPC SLP Low Profile Cap 16 IN 406 mm 15 IN 381 mm 16 11 16 IN 424 mm 9 3 16 IN 233 mm 4 1 2 IN 114 mm 16 11 16 IN 424 mm 13 5 8 IN 346 mm 12 1 2 IN 318 mm 17 7 8 IN 454 mm 7 3 8 IN 187 mm 14 IN 356 mm 12 IN 305 mm ...

Page 57: ...2342 980_R8 11 14 57 DV 46DVA GCL Coaxial Colinear Appliance Connector LINK DV30B Flex Liner Kit 768 380A Stainless Steel Flex Pipe COAXIAL to COLINEAR VENTING Figure 11 5 SLP Series Vent Components A Vent Components Diagrams continued LINKSQC DV30 COPPER LINKSQB DV30 BLACK ...

Page 58: ...tall a switch lock or a wall remote control with child protection lockout feature Keep remote controls out of reach of children See your dealer if you have questions Warming Shelves Follow the instructions supplied with the warming shelves kit to install them See your dealer if you have questions Fan Follow the instructions supplied with the fan kit to operate your fan See your dealer if you have ...

Reviews: