26
Heat & Glo • SL-550TRSI-AUE • 2079-902 Rev. K • 10/08
Figure 44.
1.6 FINISHING
The minimum clearance to combustibles are 0 from
the sides, fl oor, back and top (these clearances are
defi ned by the standoffs). The minimum distance to the
perpendicular side wall extending past the appliance
front is 51 mm. Clearance to a mantelpiece is shown
in Figure 44.
IF JOINTS BETWEEN THE FINISHED WALLS AND
THE HEATER SURROUND (TOP AND SIDES) ARE
SEALED, A 149° C. MINIMUM SEALANT MATE-
RIAL MUST BE USED. THESE JOINTS ARE NOT
REQUIRED TO BE SEALED. ONLY NON-COMBUS-
TIBLE MATERIAL (USING 149° C MINIMUM ADHE-
SIVE, IF NEEDED) CAN BE APPLIED AS FACING TO
THE HEATER SURROUND. SEE FIGURE 44.
13 mm
0
SIDE SEAL
JOINT
TOP SEAL
JOINT
FINISH MATERIAL
MAY BE COMBUSTIBLE
- TOP AND SIDES
OF UNIT
CEILING
787 mm
305 mm
279 mm
254 mm
229 mm
203 mm
178 mm
152 mm
127 mm
102 mm
76 mm
51 mm
TOP FRONT EDGE
OF FIREPLACE
NON-COMBUSTIBLE
STRIP
10 mm
8 mm
12 mm
11 mm
9 mm
178 mm
152 mm
127 mm
102 mm
76 mm
51 mm