Heat & Glo • RED40, RED40ST Installation Manual • 2155-980 Rev. C • 11/13
20
Figure 4.11
INSTALLED
HORIZONTALLY
H
1
H
2
V
1
V
2
Top Vent - Vertical Termination
Venting with 3 elbows
Note
: Use DVP Series
components only.
V
1
+ V
2
Minimum
H
1
+ H
2
Maximum
1 ft.
305 mm
2 ft.
610 mm
2 ft.
610 mm
4 ft.
1219 mm
3 ft.
914 mm
9 ft.
2743 mm
4 ft.
1219 mm
12 ft.
3658 mm
5 ft.
1524 mm
15 ft.
4572 mm
V
1
+ V
2
+ H
1
+ H
2
= 63 ft. (19.2 m) Maximum
H
1
+ H
2
= 23 ft. (7.1 m) Maximum
Note:
12 inches minimum vertical is
required prior to attaching any elbow
to the appliance.
NOTE
: Maximum total vent run= Total vertical vent run + Total horizontal vent run
MAXIMUM
VERTICAL
DROP
FROM
APPLIANCE
DIRECT VENT WITH 5 in. / 8 in. DIAMETER DVP PIPE
MAX. ELBOWS
(45° & 90°)
MAX. TOTAL VENT
RUN (FT.)
MAX. VERT.
DROP (FT.)
8
80 ft.
12 ft.
Note
: The RED40 has been approved for use with
the PVK-80 power vent system.
Figure 4.12 Power Vent
NOTICE:
If a a pipe con
fi
guration includes a vertical component
that goes downward, a vertical component going back upward
is not allowed.