HearthStone Bennington 8350 Owner'S Manual Download Page 9

HearthStone 

Quality Home Heating Products Inc 

®  

                                                                                                                                                                 Bennington  Model 8350            

8

AND STOVE TO EDGE CLEARANCES 

MINIMUM FLOOR PROTECTOR SIZE 

 

For horizontal chimney connector installations, the floor 
protection must be installed beneath the connector and 2” 
beyond each side. 
 
To determine the R-value of the proposed alternate floor 
protector: 
 

• 

Use either the K-factor or the C-factor formula 
explained above to convert specifications not 
expressed as R-values. 

 

• 

For multiple layers of floor protectors, simply add the 
R-values of each layer to determine the overall R-
value. 

 
If the overall R-value of your setup is greater than the  
R-value of the specified floor protector, then your setup is 
acceptable. 
 

F

ABRICATING A 

H

OMEMADE 

F

LOOR 

P

ROTECTOR

 

 
You can make your own floor protector by stacking 
together noncombustible materials from the following 
table.  Simply add together the listed R-values to attain 
the necessary requirements for installing your stove. 
 
The hearth pad or floor protector for the stove must have 
minimum dimensions of 39" x 48" -US (107cm x 127 cm-
CA) and must be placed as illustrated above. It must 
extend, 16 inches -US (46 cm -CA) beyond the front door, 
16 inches -US (46 cm -CA) beyond the side door, and 8 
inches (20 cm) beyond each side of the fuel loading and 
ash removal opening(s).   
 
To fabricate a floor protector for a wood floor with an 
 R-value of at least 0.9, consider the following examples: 
 
¼” mineral wool insulation 

0.78 

½” plaster board   

 

0.45 

Total R-value 

 

 

1.23 

 
   

½” Wonderboard   

 

0.20 

4” solid clay brick 

 

0.80 

Total R-value 

 

 

1.00 

 
Noncombustible Material 

Thickness 

R-value 

Gypsum or plaster board

½” 

0.45 

Wallboard, Wonderboard, or 
Durock

½” 

0.20 

Ceramic board (Fiberfrax or 
Micor)

½” 

1.10 

Nominal solid clay brick

1” 

0.20 

Ceramic wall or floor tile

¼” 

0.01 

Mineral wool insulation

1” 

3.12 

Cement mortar

1” 

0.20 

Horizontal still air

2* 

1/8” 

0.92 

*Note:  You cannot “stack” horizontal still air to 
accumulate R-values; you must separate each layer of the 
horizontal still air with another noncombustible material
 

 

 

 

1

 

According to Intertek Testing Services, Inc.

 

2

 

According to ASHRAE Handbook of Fundamentals 1977

 

 

O

UTSIDE 

A

IR 

S

UPPLY

 

 
An outside air source may be connected directly to this 
stove using an outside air adaptor. The advantage of 
providing outside air directly to the stove is that the air 
used by the stove for combustion is taken from outside of 
the residence rather than from within the room where the 
stove is located.  With outside air supplied directly to the 
stove, drafts within the room and air infiltration within the 
building are reduced.  Use of the outside air adaptor may 
also improve stove performance in a particularly airtight 
house. The outside air adaptor for this stove allows for the 
direct connection of the stove's air intake to a minimum 
3" (76 mm) diameter duct (supplied by others) which 
leads to the outside of the house.  When considering 
placement of the duct from the outside of the house to the 
hearth, keep in mind the need to avoid structural members 
of the house. See illustration for all connection options.  
Choose which is most convenient.  The termination of the 
duct on the outside wall of the house should be located in 
such a manner as to preclude the possibility of obstruction 
by snow, leaves or other material and should be screened 
against animals and insects.

 

   

REAR

VIEW

VIEW

SIDE

Summary of Contents for Bennington 8350

Page 1: ...fire follow the installation instructions Failure to follow these instructions may result in property damage bodily injury or even death SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE Bennington Model...

Page 2: ...mponents of a Venting System 10 Installing a Venting System 11 CONNECTING YOUR WOOD STOVE 11 Connecting to a Prefabricated Metal Chimney 11 Connection To A Masonry Chimney 13 INSTALLING IN A MOBILE HO...

Page 3: ...eilings hearth and other combustible surfaces This will help reduce the risk of fire Failure to follow these instructions can result in property damage bodily injury and even death Locate your stove i...

Page 4: ...d and the ash door closed tightly q Inspect the stovepipe chimney connector and chimney as recommended q Be sure the removable ash lip is in place while using the stove If the ash lip is not installed...

Page 5: ...ct all door gasket material and replace if worn frayed cracked or extremely hard EMERGENCY PROCEDURES If you have a stovepipe or chimney fire follow these instructions 1 If the fire is too threatening...

Page 6: ...efficiency combustion you desire This new technology will not corrode rust dissolve or lose its strength however it is vulnerable to puncture or cracking due to rough handling PLEASE EXERCISE CARE WH...

Page 7: ...om 15 to 36 lbs per cubic foot depending on type of wood moisture content packing density and other factors As a constant for comparison and test purposes we are assuming 20 lbs of seasoned hardwood p...

Page 8: ...e Protection Agency NFPA approved wall protection system Please refer to NFPA 211 for specifications and complete details You can obtain this information directly from NFPA National Fire Protection Ag...

Page 9: ...kness R value Gypsum or plaster board1 0 45 Wallboard Wonderboard or Durock1 0 20 Ceramic board Fiberfrax or Micor 1 1 10 Nominal solid clay brick1 1 0 20 Ceramic wall or floor tile1 0 01 Mineral wool...

Page 10: ...EARANCES TO COMBUSTIBLES from closest point of stove Unprotected Surfaces Protected Surfaces NFPA 211 Parallel Corner Parallel Corner Installation type Side Rear Side Rear single wall connector R 18 i...

Page 11: ...y connector shall not pass through floor or ceiling nor any attic or roof space closet or similar concealed space Where passage through a wall or partition of combustible construction is desired the i...

Page 12: ...2 3 mm x 13 mm sheet metal screws into the holes pre drilled in the flue collar Leaving off the screws can cause joints to separate from the vibration that results from a creosote chimney fire You can...

Page 13: ...then up the outside of the residence Whenever possible choose an interior chimney An interior chimney heats up more quickly and retains its heat thus promotes a better draft and dis courages the forma...

Page 14: ...size for best results An oversized flue will contribute to the accumulation of creosote Use the following checklist to ensure that your masonry chimney meets these minimum requirements Chimney wall co...

Page 15: ...9196N 8DP MH 8 Diameter S N 9296N Each kit includes Stainless spark arrester cap storm collar Adjustable vented flashing 0 12 6 12 Two 24 Dura Plus chimney pipes 24 support box with built in starter s...

Page 16: ...OOR FRONT DOOR HANDLE HOLDER then close the right door tightly and lower the handle to the 4 o clock position Pull on the door handle to make sure it is properly latched then remove the handle Your ha...

Page 17: ...s for stacking an old Vermonter said The spaces between the logs should be large enough for a mouse to get through but not for the cat that s chasing it Firewood should not be stored within the stove...

Page 18: ...per Kindling should be approximately ten pieces 1 2 13 mm in diameter and 10 to 18 254 to 457 mm long 2 Fully open the primary air control by pushing the lever down 3 Light the paper under the kindlin...

Page 19: ...shes as described below Re insert the ash pan by pushing it in all the way Be sure that the ash pan has been pushed firmly into place Alternately the ashes can be removed with a shovel through the sid...

Page 20: ...ately to fully press the gasket into place and assure a positive seal We require the use of the following gaskets GLASS 60 1524 mm Length 3 4 19 mm Wide Adhesive Backed Black Tape DOOR 60 1524 mm Leng...

Page 21: ...sulated the number and size of glass windows the tightness of outside doors and the construction or style of your house vaulted ceilings or other open spaces which collect large percentages of heat ce...

Page 22: ...e Connected to the Flue Disconnect all other appliances and seal openings BACK PUFFING OR GAS EXPLOSIONS Operating Technique Fully open the primary air control one minute before opening the door and k...

Page 23: ...45 FRONT 5350 071 SECONDARY AIR TUBE 1 2310 548 AIR CONTROL HANDLE 5350 072 SECONDARY AIR TUBE 2 2310 550 ASH DOOR 5350 073 SECONDARY AIR TUBE 3 2310 560 ASH LIP 5350 012 ASH DOOR HINGE L 2310 565 RIG...

Page 24: ...HearthStone Quality Home Heating Products Inc Bennington Model 8350 23 SAFETY LABEL...

Page 25: ...ponents electrical components and other components or accessories used in conjunction with the installation of the Woodstove not manufactured or supplied by HearthStone against breakage or malfunction...

Page 26: ...tone or a Dealer or allow a Dealer to make a service call at the place where the Woodstove is located In the event the Original Purchaser refuses to allow a Dealer to make a service call HearthStone o...

Reviews: