HearthStone Quality Home Heating Products, Inc ®
31
WFP-75 Model 8411
OPTION #3 - INSTALLATION RAISED MORE THAN 4" FROM FLOOR
•
When the fireplace is installed on a raised base of more than 4 inches
(C)
, non-combustible floor
protection must be used. No R value is required. The non-combustible hearth extension floor area must
extend at least 16" (406 mm)
(B)
in front of the hearth.
•
The upper and lower angle, for the full width of the floor protection, must be protected 2" horizontally and
2" vertically (
E
) by a bent and continuous piece of sheet metal (not included). Apart from these two
corners, the sheet metal does not have to cover the rest of the wall between the base of the fireplace and
the floor.
•
An 80" clearance between the fireplace base and the ceiling
(A)
must be respected.
MINIMUM MEASUREMENTS
A
80" (2032 mm)
B
16" (406 mm)
C
More than 4" (102 mm)
E
2" (51 mm)