Healy VP1000-5 Troubleshooting Manual Download Page 16

16

OUTPUT 1

1

2

OUTPUT

OUTPUT 2

COM 3 & 

4

COM 1 & 

2

COM 3 & 

4

COM 1 & 

2

CHANNEL 1 INPUT

CHANNEL 2 INPUT

TEACH

JUMPER

FAULT INPUT

FA

UL

T

POWE

R

FAULT COMMON

4 3 2 1

4 3 2 1

POWER IN

NEUTRA

L

NEUTRA

L

NEUTRA

L

NEUTRA

L

MO

TO

R

PWR RESET

COM 3&

4

COM 1&

2

COM 3&

4

COM 1&

2

Ch. 1 Input

Signals 

Ch. 2 Input

Signals 

Check for any input signal 

voltage 5 -120V AC or DC 

between each channel input 

and corresponding channel 

COM.

To neutrals from 

solenoid valves

Red
Red

Red / White

Red / White

 Whit

e

 Blac

k

 White

 Black

Orange

Purple

- With no input voltage, 0VDC should 

be measured between either red and 

orange wires.

- When input voltage is present, 

2.5VDC should be measured 

between either red and orange wires.

- When no fault is present, 5VDC 

should be measured between purple 

and orange wires.

- When fault is present, 0VDC should 

be measured between purple and 

orange wires. 

6  5  4  3  2  

1

COM 1

COM 2

NC 2

NO 2

NC 1

NO 1

To solenoid neutrals 

connected to 

dispenser electronics

Fault Relay Shown De-energized

Constant 110 VAC should 

be present between motor 

and neutral terminals 

supplying the VP1000

110 VAC power for Healy 

equipment measured 

between power in and 

neutral

(Universal Wiring Shown)

Appendix E

MC100-1 Voltage Checks

Use extreme care and caution when performing the voltage checks listed below. Up to 110 VAC is 

present creating a risk of electrical shock. 

If 110 VAC is accidentally applied to the fault or DC terminals, the module will be damaged.

Warning

Caution

Summary of Contents for VP1000-5

Page 1: ...anklin Fueling Systems 3760 Marsh Rd Madison WI 53718 USA Tel 1 608 838 8786 800 225 9787 Fax 1 608 838 6433 www franklinfueling com Manual Revision Date Changes from Previous Revision 405291001 2 Mar...

Page 2: ...Under Current Fault Troubleshooting 8 Section Four Over Current Fault Troubleshooting 9 Section Five VP1000 5 Performance Testing 10 Appendix A VP1000 5 Installation and Testing 12 Appendix B Side B...

Page 3: ...environment or by using any other reasonable means available to ensure the safety of service personnel Follow all federal state and local laws governing the installation of this equipment When no oth...

Page 4: ...202 A Healy Phase II System outside California in North America includes one VP1000 5 vacuum pump per dispenser and the appropriate Healy hanging hardware including Model 800 nozzles at each fueling...

Page 5: ...nstalled per dispenser to accommodate the vapor recovery needs for both sides of the dispenser When the dispenser is authorized the MC100 1 will activate the VP1000 5 simultaneously and run at a low s...

Page 6: ...oduct The MC100 1 s solenoid disconnect relay provides interruption of the solenoid valve neutral circuit when the VP1000 5 is in a fault state Figure 2 describes the meanings of the indicator lights...

Page 7: ...Performance Testing in Section 5 Is a fault condition present on the MC100 1 Reset the system by removing the white reset plug on the MC100 1 for a minimum of 20 seconds Re insert the white reset plu...

Page 8: ...er VR 201 No Verify the performance of the VP1000 5 per B 5 of the A B sheet Refer to Appendix B Yes Is the vacuum level produced by the VP1000 5 between 60 90 WC Disconnect the white reset plug on th...

Page 9: ...the VP1000 5 between 60 90 WC Disconnect the white reset plug on the MC100 1 Remove the VP1000 5 front cover to evaluate the rotor vanes for wear and or damage Refer to Appendix C Check for debris and...

Page 10: ...mance of the VP1000 5 per B 5 of the A B sheet Refer to Appendix B Is the vacuum level produced by the VP1000 5 between 60 and 90 WC Disconnect the white reset plug on the MC100 1 Remove the VP1000 5...

Page 11: ...e VP1000 5 increase from low to high speed when both sides of the dispenser are activated Verify the wiring of the MC100 1 Refer to Appendix E No Retest Continued from previous page Remove the vacuum...

Page 12: ...ow shows a vacuum gauge face with the acceptable vacuum level highlighted when measured with a VP1000 5 vacuum pump The acceptable vacuum level from the VP1000 5 is between 60 and 90 WC Readings of 3...

Page 13: ...est until all leaks have been repaired 8 Record data in Section B 4 Note If the initial vacuum reading is less than 60 wc it could indicate a problem with the VP1000 Remove the dispenser from service...

Page 14: ...e damage use a lint free cloth with isopropyl alcohol to clean the rotor and vanes 9 Using a lint free cloth with isopropyl alcohol thoroughly clean the inside of the pump ring and rear of the pump ca...

Page 15: ...activate Note For unihose dispensers conduct individual tests for each product grade on each side of the dispenser to ensure that the same LED activates for all grades on the same side If the other L...

Page 16: ...C should be measured between either red and orange wires When no fault is present 5VDC should be measured between purple and orange wires When fault is present 0VDC should be measured between purple a...

Page 17: ...ACH and JUMPER terminals to create a short 3 With the jumper wire in place re insert the white reset plug The yellow power light should now be illuminated 4 Authorize a nozzle on Side A of the dispens...

Page 18: ...P1000 MC100 interface check one Red Light is FLASHING over current Red Light is SOLID under current Red Light is OFF Dispenser Integrity inches of water column Starting Vacuum ________ Ending Vacuum _...

Page 19: ...19 2012 FFS 405291001 Rev2...

Reviews: