Healy VP1000-5 Troubleshooting Manual Download Page 10

10

Section Five: VP1000-5 Performance Testing

This section of the guide is to assist installers, operators, and other personnel on properly troubleshooting the 

 

VP1000-5 when no fault condition is present upon arrival at the site.

Perform a dispenser vacuum integrity test per steps 

B-3 and B-4 of the A/B sheet (Refer to Appendix B).

Does the 

integrity test pass?

Confirm that meter creep is not present. Check for leaks in 

the vapor piping (Loose fittings, Pipe

 

tape missing from 

threaded connections), hanging hardware (O-rings / quad 

ring damage), and perform a bag test at each nozzle on the 

affected dispenser.

No

Yes

Retest

Review Maintenance Log and ISD 

Warning/Failure alarms for recent activity.

Verify the performance of the VP1000-5 per B-5 of 

the A/B sheet. Refer to Appendix B)

Is the 

vacuum level produced 

by the VP1000-5 between 

60 and 90" 

WC?

Disconnect the white reset plug on the MC100-1. Remove 

the VP1000-5 front cover to evaluate the rotor/vanes for 

wear and/or damage. Refer to Appendix C. Confirm that no 

vanes are missing or stuck in the rotor. Check for debris 

and/or damage to the cover assembly. Confirm that the 

VP1000-5 shaft can turn freely by hand

No

Yes

Install a 0-100" WC vacuum gauge at the test tee.

Retest

Is the 

VP1000-5 running at 

low or high speed when neither 

side of the dispenser is authorized 

and the ambient temperature 

is above 40ºF?

Check for a leaking input voltage. Refer to Appendices E and F.

Yes

No

Continued on 

next page

To ensure accurate testing results, service personnel must 

control both sides of the dispenser by using cones and/or a 

service vehicle to block the entire dispenser.

Summary of Contents for VP1000-5

Page 1: ...anklin Fueling Systems 3760 Marsh Rd Madison WI 53718 USA Tel 1 608 838 8786 800 225 9787 Fax 1 608 838 6433 www franklinfueling com Manual Revision Date Changes from Previous Revision 405291001 2 Mar...

Page 2: ...Under Current Fault Troubleshooting 8 Section Four Over Current Fault Troubleshooting 9 Section Five VP1000 5 Performance Testing 10 Appendix A VP1000 5 Installation and Testing 12 Appendix B Side B...

Page 3: ...environment or by using any other reasonable means available to ensure the safety of service personnel Follow all federal state and local laws governing the installation of this equipment When no oth...

Page 4: ...202 A Healy Phase II System outside California in North America includes one VP1000 5 vacuum pump per dispenser and the appropriate Healy hanging hardware including Model 800 nozzles at each fueling...

Page 5: ...nstalled per dispenser to accommodate the vapor recovery needs for both sides of the dispenser When the dispenser is authorized the MC100 1 will activate the VP1000 5 simultaneously and run at a low s...

Page 6: ...oduct The MC100 1 s solenoid disconnect relay provides interruption of the solenoid valve neutral circuit when the VP1000 5 is in a fault state Figure 2 describes the meanings of the indicator lights...

Page 7: ...Performance Testing in Section 5 Is a fault condition present on the MC100 1 Reset the system by removing the white reset plug on the MC100 1 for a minimum of 20 seconds Re insert the white reset plu...

Page 8: ...er VR 201 No Verify the performance of the VP1000 5 per B 5 of the A B sheet Refer to Appendix B Yes Is the vacuum level produced by the VP1000 5 between 60 90 WC Disconnect the white reset plug on th...

Page 9: ...the VP1000 5 between 60 90 WC Disconnect the white reset plug on the MC100 1 Remove the VP1000 5 front cover to evaluate the rotor vanes for wear and or damage Refer to Appendix C Check for debris and...

Page 10: ...mance of the VP1000 5 per B 5 of the A B sheet Refer to Appendix B Is the vacuum level produced by the VP1000 5 between 60 and 90 WC Disconnect the white reset plug on the MC100 1 Remove the VP1000 5...

Page 11: ...e VP1000 5 increase from low to high speed when both sides of the dispenser are activated Verify the wiring of the MC100 1 Refer to Appendix E No Retest Continued from previous page Remove the vacuum...

Page 12: ...ow shows a vacuum gauge face with the acceptable vacuum level highlighted when measured with a VP1000 5 vacuum pump The acceptable vacuum level from the VP1000 5 is between 60 and 90 WC Readings of 3...

Page 13: ...est until all leaks have been repaired 8 Record data in Section B 4 Note If the initial vacuum reading is less than 60 wc it could indicate a problem with the VP1000 Remove the dispenser from service...

Page 14: ...e damage use a lint free cloth with isopropyl alcohol to clean the rotor and vanes 9 Using a lint free cloth with isopropyl alcohol thoroughly clean the inside of the pump ring and rear of the pump ca...

Page 15: ...activate Note For unihose dispensers conduct individual tests for each product grade on each side of the dispenser to ensure that the same LED activates for all grades on the same side If the other L...

Page 16: ...C should be measured between either red and orange wires When no fault is present 5VDC should be measured between purple and orange wires When fault is present 0VDC should be measured between purple a...

Page 17: ...ACH and JUMPER terminals to create a short 3 With the jumper wire in place re insert the white reset plug The yellow power light should now be illuminated 4 Authorize a nozzle on Side A of the dispens...

Page 18: ...P1000 MC100 interface check one Red Light is FLASHING over current Red Light is SOLID under current Red Light is OFF Dispenser Integrity inches of water column Starting Vacuum ________ Ending Vacuum _...

Page 19: ...19 2012 FFS 405291001 Rev2...

Reviews: