LEFT DIP SWITCH PRIORITY SELECTIONS
Dip Switch 1: Zone Valve or Zone Pump
Dip Switch 3: Dual Zone Priority
Dip Switch 2: Sequential Priority
Dip Switch 4: Module Priority
OFF:
Zone Pumps.
The zone control will post purge the zones for 60 seconds. The control will also excercise the
pumps every 72 hours.
ON:
Zone Valves. If this is selected, there will be no post purge time, and the system pump output will be on
after a period of 60 seconds.
OFF:
No dual zone priority.
ON:
Dual Zone Priority. This dip switch position allows the user to set dual zone priority for zones 1 and 2 over
zones 3 and 4.
NOTE: Dip switchs 2 and 3 cannot be selected together. Select only one or the other.
OFF:
No sequential priority
ON:
Sequential priority on. This dip switch position allows the user to prioritize zone 1 over 2 over 3 over 4.
OFF:
No Module priority
ON:
Module priority on. This dip switch position allows the user to prioritze one module over the next one. This
feature will shut off the zone controls to the right of the one with this dip switch selected.
NOTE: Module priority can be used in conjunction with other priorities.