HBX ZON-0500 Installation Manual Download Page 12

H B X   Z O N - 0 5 0 0   Z o n e   C o n t r o l

V e r s i o n   2 . 2 0

Zone-0500 Manual Page 10 

RIGHT DIP SWITCH SETUP

ECO-1000

The right Dip Switches  are used for setting up Heating or Cooling zones.

Dip Switch 1: Heating or Cooling Zone

Dip Switch 2-5: Heating OR Cooling Zone (

DIP 1 SET TO OFF

)

Dip Switch 2-5: Heating and Cooling OR Heating Only Zone (

DIP 1 SET TO ON

)

OFF: 

With this set up, the zones can be set to either Heating or Cooling

ON: 

This setting allows the zones to be set to either Heating or Heating and Cooling.

OFF: 

This setting will allow the user to set up the zone for heating.

ON: 

This setting will allow the user to set up the zone for cooling.

WWSD will shut off heating zones

CWSD will shut off cooling zones

OFF: 

This setting will allow the user to set up the zone for heating only.

ON: 

This setting will allow the user to set up the zone for heating and cooling (used in 2 pipe systems).

WWSD will shut off heating only zones

CWSD or WWSD will shut off their respective parts of the Heating and Cooling zones

on 

on 

on 

on 

on 

on 

on 

on 

on 

Heating & 

Cooling

OR

Heating 

Only

Heating 

OR

Cooling

on 

on 

on 

on 

on 

on 

on 

on 

on 

Heating & 

Cooling

OR

Heating 

Only

Heating 

OR

Cooling

on 

on 

on 

on 

on 

on 

on 

on 

on 

Heating & 

Cooling

OR

Heating 

Only

Heating 

OR

Cooling

on 

on 

on 

on 

on 

on 

on 

on 

on 

Heating & 

Cooling

OR

Heating 

Only

Heating 

OR

Cooling

Summary of Contents for ZON-0500

Page 1: ...HBX Control Systems Inc Installation Manual ZON 0500 Version 2 30 ZON 0500 Zone Control...

Page 2: ...o n t r o l V e r s i o n 2 2 0 Table of Contents TABLE OF CONTENTS Introduction 1 3 Safety Symbols Warnings 1 Receipt Inspection 1 Description 2 Technical Data and Dimensions 3 Wiring Installation 4...

Page 3: ...h caution Moderate Hazard This action may cause personal injury or have adverse effects on the installation process if handled incorrectly Disconnect Power Source The presence of low voltage 24VAC or...

Page 4: ...alone unit Expandable to 36 zones Provides pump or valve control Boiler enable TT contacts 2 demand outputs Heat Cool or TT DHW Multiple priority selections see page 7 Heating zones will not open or...

Page 5: ...Input 120VAC 16A Max 1 x Pump Relay 120VAC 5A Combined relay power should not exceed 20A Weight 0 408Kg Dimensions 100mm W x 168mm H x 70mm D ETL Listings Meets CSA C22 2 No 24 Meets UL Standard 873...

Page 6: ...se outputs are used to power the thermostats and are rated for 24VAC at 6VA Zone 4 Thermostat Zone 3 Thermostat Zone 2 Thermostat Zone 1 Thermostat Demand Output DHW or Heating Demand Output Boiler TT...

Page 7: ...and pins When installed correctly there is virtually no gap be tween units With power applied to the assembly the first green LED should be illuminated on each Expansion Module This lit green LED ser...

Page 8: ...zone post purge time Dip switches 2 5 on the right set of dip switches correspond to zones 1 4 and dipswitch 1 is used to modify the type of demand signal sent to the main controller when used as an...

Page 9: ...er a period of 60 seconds OFF No dual zone priority ON Dual Zone Priority This dip switch position allows the user to set dual zone priority for zones 1 and 2 over zones 3 and 4 NOTE Dip switchs 2 and...

Page 10: ...es Dip Switch 2 5 Use As Heating OR Cooling Demands Use this configuration with ECO units Dip Switch 2 5 Use As Low Temp OR High Temp Demands Use this configuration with CPU units OFF This position wi...

Page 11: ...ter DHW Priority Dip Switch 2 5 Heat Demand Zone Dip Switch 2 5 Low High Temperature Zone OFF No DHW priority ON This Dip Switch allows the zone controls to receive a DHW priority from the CPU 1000 If...

Page 12: ...e zone for heating ON This setting will allow the user to set up the zone for cooling WWSD will shut off heating zones CWSD will shut off cooling zones OFF This setting will allow the user to set up t...

Page 13: ...RL 8 7 1 RL 1 RL 6 5 1 RL 1 RL 4 3 1 RL 1 RL 2 1 1 2 2 1 2 TT CD 2 4 3 2 DHW HD 2 TH 6 5 2 TH 2 TH 8 7 2 TH 2 TH 10 9 2 TH 2 TH 12 11 2 TH 2 24V AC 14 13 2 2 3 4 1 2 3 4 5 1 Demand Outputs Thermostat...

Page 14: ...5 2 TH 2 TH 4 3 3 Thermostat RL 1 RL 2 1 1 2 A DO NOT CONNECT POWER HERE THM 0100 HBX 2 24V AC 6 5 2 TH 2 TH 4 3 3 Thermostat RL 1 RL 2 1 1 2 A DO NOT CONNECT POWER HERE System Pump Zone 1 Zone 2 Zone...

Page 15: ...A 24 VAC out to thermostats 6VA Max 2 24V AC 16 15 2 GR 120 15 N L 14 13 RL 1 RL 12 11 1 RL 1 RL 10 9 1 RL 1 RL 8 7 1 RL 1 RL 6 5 1 RL 1 RL 4 3 1 RL 1 RL 2 1 1 2 2 1 2 TT CD 2 4 3 2 DHW HD 2 TH 6 5 2...

Page 16: ...ZON 0500 HBX Zone Control DO NOT CONNECT POWER HERE 5A 5A 5A 5A 5 A 24 VAC out to thermostats 6VA Max 2 24V AC 16 15 2 GR 120 15 N L 14 13 RL 1 RL 12 11 1 RL 1 RL 10 9 1 RL 1 RL 8 7 1 RL 1 RL 6 5 1 R...

Page 17: ...HD 2 TH 6 5 2 TH 2 TH 8 7 2 TH 2 TH 10 9 2 TH 2 TH 12 11 2 TH 2 24V AC 14 13 2 2 3 4 1 2 3 4 5 1 Demand Outputs Thermostat Imputs 1 2 DS 1 DS 1 3 4 DS 2 DS 2 5 6 DS 3 DS 3 GR 120 28 N L 27 26 GR 120 2...

Page 18: ...HP 2 1 2 DS 1 DS 1 3 4 DS 2 DS 2 5 6 DS 3 DS 3 GR 120 28 N L 27 26 GR 120 25 N L 24 23 GR 120 22 N L 21 20 GR 120 19 N L 18 17 RL 2 RL 16 15 2 RL 1 RL 14 13 1 TM 3 TM 12 11 3 TM 2 TM 10 9 2 TM 1 TM 8...

Page 19: ...chasers sole remedy shall be at HBX s option repair or replacement The foregoing warranties and remedies are exclusive and in lieu of all other warranties expressed or implied either in fact or by ope...

Page 20: ...HBX Control Systems Inc 2016 Phone 1 403 720 0029 Fax 1 403 720 0054 Email info hbxcontrols com Web www hbxcontrols com HBX Control Systems Inc 4516 112th Avenue SE Calgary AB Canada T2C 2K2...

Reviews: