© 2014 HBX Controls

4

1) TYPE 

HEAT ONLY

2) C OR F 

  

°F

3) VIEW ALL 

  YES

4) VIEW AUTO 

  YES

5) SETBACK  

  YES 

 

6) ROOM OFFSET   0

°

F

SPECIAL FUNCTIONS

     View All/Hide All 

 

Select 

“No”

 to turn off 

“Status Screen”

  information 

and provide a simplified information readout of the 

“Status Screen”

. This option turns off any extra sensor 

readings on the control. 

72.0

°F

10:00

am

MON

ROOM

“View All” = No

HT

HT

   =  Heat On

HT2 

=  Stage 2 Heat On

CL

   =  Cool On

CL2

  =  Stage 2 Cool On

FN

   =  Fan On

72.0

°F

ROOM

FLOOR

79°F

TARGET

72°F

HT

“View All” = Yes

10:00

am

MON

----

OFF

HD

ON/OFF = 

displays the activity status of the 

boiler (off or on) in boiler mode

HD = 

shows a heat demand in boiler mode

---- = 

displays when no sensors are 

connected

1) TYPE 

HEAT ONLY

2) C OR F 

  

°F

3) VIEW ALL 

  YES

4) VIEW AUTO 

  YES

5) SETBACK  

  YES 

 

6) ROOM OFFSET   0

°

F

SPECIAL FUNCTIONS

     View Auto 

This feature allow you automatic changeover or 

manual changeover. Changeover refers to the 

thermostat being switched from heat to cool as the 

air crosses a certain temperature. Auto changeover 

switches from heat to cool automatically while 

manual changeover thermostats must be changed 

by hand. If you select “NO”, changeover is not going 

to appear in the Adjustment screen.

Applicable to: Heat/Cool, 2Heat/Cool and 2Cool/Heat modes. 

1) TYPE 

HEAT ONLY

2) C OR F 

  

°F

3) VIEW ALL 

  YES

4) VIEW AUTO 

  YES

5) SETBACK  

  YES 

 

6) ROOM OFFSET   0

°

F

SPECIAL FUNCTIONS

     Setback 

 

Allows you to program a setback. A setback can 

be programmed to maximize energy during time 

frames where the zone may be vacant. When you 

select “YES” you can program up to 4 setback time 

period.

1) TYPE 

HEAT ONLY

2) C OR F 

  

°F

3) VIEW ALL 

  YES

4) VIEW AUTO 

  YES

5) SETBACK  

  YES 

 

6) ROOM OFFSET   -1

°

F

SPECIAL FUNCTIONS

     Offset 

 

This feature allows you to program an offset. In the 

case that the thermostat is not reading the same 

temperature as the actual temperature in the 

room. This setting allows the used to offset the 

temperature showing on the thermostat.

eg. 

Actual Room Temperature 72 °

 

  Thermostat Shows 73 °            

 

  The user can put an offset of -1 ° to get the tempratures to match.

Summary of Contents for THM-0200

Page 1: ...HBX Control Systems Inc Installation Manual THM 0200 Programmable Thermostat Version 1 07 THM 0200...

Page 2: ...ith the codes and practices applicable to the jurisdiction for the actual installation The HBX THM 0200 is a microprocessor based controller and as such is not to be regarded as a safety limit control...

Page 3: ...evening and sleep and weekend settings The THM 0200 has two external sensor inputs and multiple heating and cooling modes and can function as a single boiler reset control Some features of the THM 020...

Page 4: ...tons simultaneously for 5 seconds from the Status Screen To select the desired option use the and buttons to toggle and the set button to select 1 Type SelectbetweenHeating Cooling Boiler andavarietyo...

Page 5: ...SPECIAL FUNCTIONS 2 Cool Heat Function Select the 2 Cool Heat Function for applications using 2 stage cooling and 1 stage heating See diagram 8 for wiring example 1 TYPE 2COOL HEAT 2 C OR F F 3 VIEW A...

Page 6: ...witched from heat to cool as the air crosses a certain temperature Auto changeover switches from heat to cool automatically while manual changeover thermostats must be changed by hand If you select NO...

Page 7: ...the previous screen START HEAT 1 6 00A 74 F 2 8 00A 64 F 3 4 30P 72 F 4 9 00P 90 F 5 BACK WEEKDAY PROGRAMS Weekend Programs Adjust four time periods within the two weekend program menu The Back option...

Page 8: ...RM Ave averages external 1 and internal sensor Floor displays the floor temperature using external 1 sensor 1 WEEKDAY 2 WEEKEND 3 HOLD TEMP 76 F 4 MODE ROOM 5 SENSOR1 NONE 6 SENSOR2 NONE ADJUSTMENTS R...

Page 9: ...s external 1 2 sensors using floor temperature Outdoor will use external 2 sensor to display outdoor temperature 2 WEEKEND 3 HOLD TEMP OFF 4 MODE FLOOR 5 DIFF 6 F 6 SENSOR1 FLOOR 7 SENSOR2 OUTDOOR ADJ...

Page 10: ...al sensor uses external sensor 2 4 MODE DUAL 5 FLOOR MAX 78 F 6 FLOOR MIN 69 F 7 SENSOR 1 FLOOR 8 SENSOR 2 NONE 9 TIME 5 18AM ADJUSTMENTS Dual Mode Continuous Fan ON Enables the fan to run continuousl...

Page 11: ...both condensing and non condensing boilers Setupasperboilermanufacturersrecommendation BOILER ADJUSTMENTS 1 MAX BOILER 190 F 2 MIN BOILER 120 F 3 OUT DESIGN 10 F 4 DIFF 10 F 5 WWSD 72 F 6 DHW PRTY OFF...

Page 12: ...g Examples 5 4 3 2 1 6 7 8 9 10 1 2 3 Output 1 and 2 4 5 Dry Contact Output 6 7 8 External Therm 1 and 2 9 10 Power In the following examples extra thermistors are not needed on pins 6 8 and 7 8 These...

Page 13: ...R HERE TH 1 6 RL 1 2 A 1 Y G THM 0200 Thermostat Transformer R C 24VAC 3 Room Only Cooling Fan THM 0200 HBX RL 2 RL 3 2 2 2 24V AC 10 9 2 TH 2 TH 8 7 3 Thermostat RL 1 RL 5 4 1 2 A DO NOT CONNECT POWE...

Page 14: ...2 TH 8 7 3 Thermostat RL 1 RL 5 4 1 2 A DO NOT CONNECT POWER HERE TH 1 6 RL 1 2 A 1 Heat Fan Cool Transformer R C 24VAC 4 Heating and Cooling Fan HBX RL 2 RL 3 2 2 2 24V AC 10 9 2 TH 2 TH 8 7 3 RL 1...

Page 15: ...2 24V AC 10 9 2 TH 2 TH 8 7 3 Thermostat RL 1 RL 5 4 1 2 A DO NOT CONNECT POWER HERE TH 1 6 RL 1 2 A 1 Transformer R C 24VAC HBX RL 2 RL 3 2 2 2 24V AC 10 9 2 TH 2 TH 8 7 3 RL 1 RL 5 4 1 2 A DO NOT CO...

Page 16: ...s a 30 second pre purge and 60 second post purge Boiler Enable Outdoor Sensor Boiler Sensor Transformer R C 24VAC 9 Boiler THM 0200 HBX RL 2 RL 3 2 2 2 24V AC 10 9 2 TH 2 TH 8 7 3 Thermostat RL 1 RL 5...

Page 17: ...15 NOTES...

Page 18: ...2014 HBX Controls 16 NOTES...

Page 19: ...on repair or replacement The foregoing warranties and remedies are exclusive and in lieu of all other warranties expressed or implied either in fact or by operation of law statutory or otherwise inclu...

Page 20: ...V1 02 Toll Free Technical Support 1 855 554 6629...

Reviews: