HBX Control Systems Inc.

Installation Manual

ZON-0550

Version 2.02

ZON-0550

• Zone Control 

Summary of Contents for ThermoLinx TMX-0100

Page 1: ...HBX Control Systems Inc Installation Manual ZON 0550 Version 2 02 ZON 0550 Zone Control ...

Page 2: ...2 User Interface Indicator LEDs 3 Technical Data and Dimensions 4 5 Wiring Installation 6 25 Wiring 6 Installation 7 Sequence of Operation 8 WiFi System Setup 9 Connect to a Wireless Network 10 11 Add Thermostats 12 13 ThermoLinx App Initial Setup 14 ThermoLinx App Alarms 15 ThermoLinx App Advanced Settings 16 17 Pairing Multiple Zone Controls 18 21 Application Drawing 18 28 Troubleshooting Guides...

Page 3: ...jury or permanent damage to components or equipment Point of Interest This point clarifies pertinent information or brings your attention to an action that may have adverse effects on the installation process Drawing Reference Refer to the specified electrical or mechanical drawing at the back of the manual The HBX ZON 0550 is a microprocessor based controller and as such is not to be regarded as ...

Page 4: ...ablet device App for remote access Control four 4 independent zone per control plus Fancoil W Y G output Wirelessly expandable to a maximum of twenty 20 zones Provides pump valve or damper control Humidity Control X Output Two 2 demands outputs Heat Cool or LT HT Geo Mode 2 or 4 pipe systems Alarm email notification PUMP ZN1 N H ZN1 N H ZN2 N H ZN3 N H ZONE PWR N H POWER L N R W Y G X LT CD HT HD ...

Page 5: ... 0550 Zone Control Relays 240VAC 5A Max Input 120VAC 15A Max Zone 1 POWER Zone 2 Zone 3 Zone 4 LT CD Heat HT HD Cool Demands Fan Humidity Fan Coil EX Normally Open Zone 1 Zone 4 Calling Heat with Fan On Normally Open Damper Zone with no call for heat cool Power is applied to close the damper because other zones are calling for heat cool There is a 1 minute delay to close the damper when another zo...

Page 6: ...elay 120VAC 5A Input 120VAC 15A Max 1 x Pump Relay 120VAC 5A 1 x Humidity Output 24VAC 2A Combined relay power should not exceed 15A Weight 0 408Kg Dimensions 121mm W x 188mm H x 66mm 4 76in W x 7 40in H x 2 60in ETL Listings Meets CSA C22 2 No 24 Meets UL Standard 873 ETL Control No 3068143 Storage 50 F to 104 F 10ºC to 40ºC ZON 0550 RF Info Contains IC 7693A 24J40MB Contains FFC ID 0A3MRF24J40MB...

Page 7: ...mm W x 62mm H x 28 24mm ETL Listings Meets CSA C22 2 No 24 Meets UL Standard 873 ETL Control No 3068143 Storage 50 F to 104 F 10ºC to 40ºC TMX 0100 RF Info Contains IC 8169A G2M5477 Contains FFC ID U3O G2M5477 LEDs Red Unit is connected to a WiFi Network Green Unit is powered Blue Unit is communicating with the server Technical Data and Dimensions Technical Data and Dimensions TMX 0100 Technical D...

Page 8: ... demands These can be a Heating and Cooling demand 24VAC contact dry contact TT Low Temperature demand for a boiler or DHW High Temperature demand 4 INPUT POWER This input is to power the ZON 0550 0 5 Amps at 120 VAC is required to power this device 5 ZONE POWER This input is used to power the zone outputs and is rated for 240VAC 120VAC or 24VAC 6 Fancoil Output These are the outputs for the Fanco...

Page 9: ... from falling water and high humidity conditions With all the covers in place it is designed to protect any individual from accidental electrical shock It is not suitable for installation in hazardous locations and should not be close to any electromagnetic fields Installation 1 Connect the THM 0300 or THM 0500 Thermostat to the control If you are using a single thermostat ensure it is connected t...

Page 10: ...e When setting the zone control for Geo Mode this will change the demand outputs from a low and high temperature to a heat or cool demand Heat demand to be wired to HT HD and Cool demand to LT CD PUMP ZN1 N H ZN1 N H ZN2 N H ZN3 N H ZONE PWR N H POWER L N R W Y G X LT CD HT HD THM1 5 6 THM2 5 6 THM3 5 6 THM4 5 6 ZON 0550 Zone Control Relays 240VAC 5A Max Input 120VAC 15A Max Zone 1 POWER Zone 2 Zo...

Page 11: ...ights on the front Red for Wi Fi Green for Ready Blue for Server Information is communicated by the color of the lights and whether they are steady or flashing The unit should be installed inside and protected from falling water and high humidity conditions With all the covers in place it is designed to protect any individual from accidental electrical shock It is not suitable for installation in ...

Page 12: ...to Wi Fi setup If the WiFi Setup page does not appear ensure that your device is connected to the ThermoLinx network in step 4 and restart the ThermoLinx app 6 In Wi Fi setup select the home Wi Fi network you would like to connect to and enter the password for the Wi Fi network Home network name cannot contain more than 30 characters The password should not contain any special characters If using ...

Page 13: ...you to Wi Fi setup If the WiFi Setup page does not appear restart the ThermoLinx app 4 In Wi Fi setup manually enter personal hotspot device name in network SSID and enter your personal hotspot password Select Connect to WiFi Now Hotspot name will not appear in network list 5 Exit the app and go back into your personal hotspot settings and wait for the ThermoLinx Network to connect your hotspot 6 ...

Page 14: ...tup Zone Setup Fancoil Setup Humidity Setup Degrees F Stage Delay 15 Mins Sync Code AAAA 1234 System Setup Zone Setup Fancoil Setup Humidity Setup Degrees F Stage Delay 15 Mins Sync Code AAAA 1234 System Setup Zone Setup Fancoil Setup Humidity Setup Degrees F Stage Delay 15 Mins Sync Code AAAA 1234 Int Fan OFF 2 hrs Fancoil Setup Fan on demand Zone on demand Temp Average None Fan Mode Int Int Fan ...

Page 15: ...ike to appear on the thermostat and app Do not use symbols ect for thermostat name 4 Select back to return to the zone home screen and select save Lost Internet Connection If all devices on the ThermoLinx app are displayed with warning icons then the system has lost internet connection You will need to reconnect the system to your network by following the steps outlined on pages 10 11 If internet ...

Page 16: ...em location by city or zip postal code Do not use spaces in Zip Postal Code 3 Change the app from Fahrenheit F to Celsius C 4 Scroll and select the system location time zone Setting time zone will automatically adjust the time on your thermostats and will automatically adjust for daylight savings 5 Enter a contractor code to unlock advanced settings options Contact HBX Tech Support for contractor ...

Page 17: ...loor or tank sensor in a zone for alarm setup 1 If thermostat is setup as a DHW Aquastat Floor Sensor will automatically change to Tank Sensor 2 Only one sensor can be monitored at a time Alarm Triggers These options allow you to select a set temperature for an alarm trigger If the temperature falls below or rises above the set temperature an alarm email notification from the HBX server will be se...

Page 18: ...utilizing normally closed dampers Dampers 2 Stage N O 1st stage is radiant and the second stage is utilizing a normally open damper Utilizing this option will require to use the next corresponding zone output to accommodate for the second stage damper This option is only available for Zones 1 and Zone 3 Dampers 2 Stage N C 1st stage is radiant and the second stage is utilizing a normally closed da...

Page 19: ...ify or dehumidify Auto Enables the thermostat to humidify or dehumidify to the target automatically based on the outdoor temperature No manual adjustment is required The zoning system must be connected to a wifi network for this feature to be applicable or the thermostat must utilize an external sensor monitoring the outdoor temperature 2 Humidity Target When humidity is set to ON manually adjust ...

Page 20: ...QUENCE 1 4 2 DEMAND LOW 3 PRIORITY NONE 4 PASSWORD AB12 5 MASTER ID A2 Master Control Steps ZONE SETUP 1 SEQUENCE 1 4 2 DEMAND LOW 3 PRIORITY NONE 4 PASSWORD AB12 5 MASTER ID A2 6 DAMPER ZONE OFF SYSTEM SETUP SYNC CODE ABCD 1234 1 ZONE SETUP 2 FANCOIL SETUP 3 C OR F F 4 STAGE DELAY 15m Pairing Multiple Zone Controls with the thm 0300 PUMP ZN1 N H ZN1 N H ZN2 N H ZN3 N H ZONE PWR N H POWER L N R W ...

Page 21: ...n for 2 seconds Select 3 System Setup and then select 1 Zone Setup using the button 2 In Zone Setup go to 1 Sequence Select the sequence you would like to set up for the control 5 8 9 12 13 16 17 20 3 Stay in Zone Setup and toggle down the menu options to 5 Paired to Zone ID 4 Select 5 Paired to Zone ID This will put the control into Pairing Mode When pairing is successful it will indicate the ID ...

Page 22: ...e TMX 0100 module 2 On the first THM 0500 thermostat zone 1 of the master zone control enter the setup menu by pressing the menu icon on the top right corner Select system setup and then select zone setup 3 In zone setup select sequence This setting allows you to set your zone control sequence order 4 In sequence set your zone control to 1 4 This will set your zone control as the master 5 Stay in ...

Page 23: ...pairing to master mode TMX 0100 must be connected only to the master zone control Zones 1 4 Paired Control Steps Zone Setup Sequence 5 8 Demand Low Priority None Password AB12 Pair to Zone ID B4 Damper Zone Off Zone Setup Pairing Successful Zone Setup Discovery Mode System Setup Zone Setup Fancoil Setup Humidity Setup Degrees F Stage Delay 15 Mins Sync Code AAAA 1234 Zone Setup Sequence 1 4 Demand...

Page 24: ...OOM HBX TH TH THM 0300 3 COMM 6 5 3 TH 2 TH 4 3 2 Thermostat 1 2 1 1 DO NOT CONNECT POWER HERE INT ROOM EXT ROOM HBX TH TH DO NOT CONNECT POWER HERE ZON 0550 Zone Control 5A 5A 5A 5A 5A 1 PUMP 1 2 1 H ZN 1 3 4 N H 5 6 N ZN 2 H 7 8 N ZN 3 H 9 10 N ZN 4 H 11 12 N ZONE POWER GR POWER 120 15 N L 14 13 1 4 3 1 LT CD 2 6 5 2 HT HD 5 THM 1 8 7 6 5 THM 2 10 9 6 5 THM 3 12 11 6 5 THM 4 14 13 6 1 2 1 1 R W ...

Page 25: ...M EXT ROOM HBX TH TH THM 0300 3 COMM 6 5 3 TH 2 TH 4 3 2 Thermostat 1 2 1 1 DO NOT CONNECT POWER HERE INT ROOM EXT ROOM HBX TH TH DO NOT CONNECT POWER HERE ZON 0550 Zone Control 5A 5A 5A 5A 5A 1 PUMP 1 2 1 H ZN 1 3 4 N H 5 6 N ZN 2 H 7 8 N ZN 3 H 9 10 N ZN 4 H 11 12 N ZONE POWER GR POWER 120 15 N L 14 13 1 4 3 1 LT CD 2 6 5 2 HT HD 5 THM 1 8 7 6 5 THM 2 10 9 6 5 THM 3 12 11 6 5 THM 4 14 13 6 1 2 1...

Page 26: ...7 6 5 THM 2 10 9 6 5 THM 3 12 11 6 5 THM 4 14 13 6 1 2 1 1 R W 2 Y G 16 15 2 Fancoil Outputs Demand Outputs Thermostat Communication Fancoil Outputs HBX X 17 2 Fancoil 1 R W Y G C C X Humidity Device Zone Pumps Zone 5 Zone 6 Zone 7 Zone 8 5 6 7 8 THM 0500 3 COMM 6 5 3 TH 2 TH 4 3 2 Thermostat 1 2 1 1 DO NOT CONNECT POWER HERE INT ROOM EXT ROOM HBX TH TH THM 0300 3 COMM 6 5 3 TH 2 TH 4 3 2 Thermost...

Page 27: ... CONNECT POWER HERE INT ROOM EXT ROOM HBX TH TH THM 0300 3 COMM 6 5 3 TH 2 TH 4 3 2 Thermostat 1 2 1 1 DO NOT CONNECT POWER HERE INT ROOM EXT ROOM HBX TH TH THM 0500 3 COMM 6 5 3 TH 2 TH 4 3 2 Thermostat 1 2 1 1 DO NOT CONNECT POWER HERE INT ROOM EXT ROOM HBX TH TH THM 0300 3 COMM 6 5 3 TH 2 TH 4 3 2 Thermostat 1 2 1 1 DO NOT CONNECT POWER HERE INT ROOM EXT ROOM HBX TH TH DO NOT CONNECT POWER HERE...

Page 28: ... 3 2 Thermostat 1 2 1 1 DO NOT CONNECT POWER HERE INT ROOM EXT ROOM HBX TH TH THM 0300 3 COMM 6 5 3 TH 2 TH 4 3 2 Thermostat 1 2 1 1 DO NOT CONNECT POWER HERE INT ROOM EXT ROOM HBX TH TH THM 0500 3 COMM 6 5 3 TH 2 TH 4 3 2 Thermostat 1 2 1 1 DO NOT CONNECT POWER HERE INT ROOM EXT ROOM HBX TH TH THM 0300 3 COMM 6 5 3 TH 2 TH 4 3 2 Thermostat 1 2 1 1 DO NOT CONNECT POWER HERE INT ROOM EXT ROOM HBX T...

Page 29: ... TH TH THM 0300 3 COMM 6 5 3 TH 2 TH 4 3 2 Thermostat 1 2 1 1 DO NOT CONNECT POWER HERE INT ROOM EXT ROOM HBX TH TH DO NOT CONNECT POWER HERE ZON 0550 Zone Control 5A 5A 5A 5A 5A 1 PUMP 1 2 1 H ZN 1 3 4 N H 5 6 N ZN 2 H 7 8 N ZN 3 H 9 10 N ZN 4 H 11 12 N ZONE POWER GR POWER 120 15 N L 14 13 1 4 3 1 LT CD 2 6 5 2 HT HD 5 THM 1 8 7 6 5 THM 2 10 9 6 5 THM 3 12 11 6 5 THM 4 14 13 6 1 2 1 1 R W 2 Y G 1...

Page 30: ...TH THM 0300 3 COMM 6 5 3 TH 2 TH 4 3 2 Thermostat 1 2 1 1 DO NOT CONNECT POWER HERE INT ROOM EXT ROOM HBX TH TH DO NOT CONNECT POWER HERE ZON 0550 Zone Control 5A 5A 5A 5A 5A 1 PUMP 1 2 1 H ZN 1 3 4 N H 5 6 N ZN 2 H 7 8 N ZN 3 H 9 10 N ZN 4 H 11 12 N ZONE POWER GR POWER 120 15 N L 14 13 1 4 3 1 LT CD 2 6 5 2 HT HD 5 THM 1 8 7 6 5 THM 2 10 9 6 5 THM 3 12 11 6 5 THM 4 14 13 6 1 2 1 1 R W 2 Y G 16 15...

Page 31: ...with those 4 zones if multiple zone modules are controlling the same system pump then the system pump outputs should be wired in parallel Check priorities settings Fancoil outputs won t turn on Verify wiring Check the demand settings See THM 0300 0500 manual A zone demand needs to be made for the fancoil output to turn on Check priorities settings Zone lights flashing The ZON 0550 is in Discovery ...

Page 32: ...rver is off and red light is on possible firewall issue or router configuration open port 1314 contact HBX technical support Blue light server is off and red light off check network name and password for special characters Check for correct network name and password possible network strength issue If there is not network password use three spaces Red light flashing Thermolinx was not initially set...

Page 33: ...sole remedy shall be at HBX s option repair or replacement The foregoing warranties and remedies are exclusive and in lieu of all other warranties expressed or implied either in fact or by operation of law statutory or otherwise including warranties of merchantability and fitness for a particular purpose application HBX neither assumes nor authorizes any other person to assume for it any other lia...

Page 34: ...H B X Z O N 0 5 5 0 Z o n e C o n t r o l V e r s i o n 2 0 2 Page 32 Notes ...

Page 35: ...H B X Z O N 0 5 5 0 Z o n e C o n t r o l V e r s i o n 2 0 2 Page 33 Notes ...

Page 36: ...tems Inc 2018 Toll Free Technical Support 1 855 410 2341 Phone 1 403 720 0029 Fax 1 403 720 0054 Email info hbxcontrols com Web www hbxcontrols com HBX Control Systems Inc 4516 112th Avenue SE Calgary AB Canada T2C 2K2 ...