Mode setup
1. Thermostat Mode: This option allows you to select between Room, Floor
and Dual Mode.
2. Sensor Type: This option allows you to select between Floor, Room, Outdoor
and Room Average sensor types.
Zone setup
1. Zone Demand: This option allows you to select between a Low
Temperature, High Temperature, Domestic Hot Water or Fancoil Demand.
2. Zone Priority: This option allows the user to set a priority on a zone(s) over
other zone(s). Priorities range from 1 (highest) to 7 (lowest). Higher priorities
will lock out lowest priorities until the demand has been satisfied. Multiple
zones can be given the same numbered priorities. The Priority Shield option
allows a zone to ignore other priorities from other zones.
Priority 1 is a timed priority of 60 minutes, generally used for DHW
Humidity settings
Humidity Settings are only available on zones using the THM-0500
Touch screen Thermostat.
3. Zone Valve: When set to ON, The zone will be utilizing a zone valve or
actuator. There will be a 60 second delay for the system pump to turn on
when there is a heat or cool demand.
Humidity setup
1. Use Humidity:
ON
– Enables the thermostat to humidify or dehumidify.
OFF
– Disables the thermostat to humidify or dehumidify.
Auto
– Enables the thermostat to humidify or dehumidify to the target %
automatically based on the outdoor temperature. No manual adjustment
is required. The zoning system must be connected to a wifi network for this
feature to be applicable or the thermostat must utilize an external sensor
monitoring the outdoor temperature.
2. Humidity Target: When humidity is set to ON, manually adjust your humidity
target.
3. Type: This option allows you the option to humidify or dehumidify.
4. Fan ON Humidity: This option will turn your fan on when there is a humidity
demand.
Reset all to factory settings
This setting will reset the zone device to its original factory settings. This process
cannot be undone.
100%
9:41 AM
MODE SETUP
ZONE SETUP
Thermostat Mode
Room
Sensor Type
None
Zone Demand
Low Temp
RESET SETTINGS
Reset ALL To Factory Settings
Zone Priority
Zone Valve
None
Off
Fan On with Demands(W,Y)
Zone On with Demands(W,Y)
Temperature Averaging
Damper Zone
None
Off
Use Humidity
Humidity Target
Type
Fan ON with Humidity
HUMIDITY SETTINGS
Humidify
10%
ON
Advanced Settings
83°F
100%
9:41 AM
Fan On with Demands(W,Y)
Zone On with Demands(W,Y)
Temperature Averaging
Damper Zone
FANCOIL SETTINGS
MODE SETUP
ZONE SETUP
None
Off
Thermostat Mode
Room
Sensor Type
None
Zone Demand
Low Temp
Zone Priority
None
Zone Valve
Off
Degrees C
Geo Mode
Use Humidity
Humidity Target
Type
Fan ON with Humidity
HUMIDITY SETTINGS
Humidify
10%
ON
Advanced Settings
83°F