H B X Z O N - 0 5 5 0 Z o n e C o n t r o l
V e r s i o n 2 . 0 2
Page 9
PUMP
ZN1
N H
ZN1
N H
ZN2
N H
ZN3
N H
ZONE PWR
N H
POWER
L
N
R W
Y G X
LT/CD
HT/HD
THM1
5 6
THM2
5 6
THM3
5 6
THM4
5 6
ZON-0550
Zone Control
Relays:
240VAC 5A Max
Input:
120VAC 15A Max
Zone 1
POWER
Zone 2
Zone 3
Zone 4
LT/CD
Heat
HT/HD Cool
Demands
Fan
Humidity
Fan Coil
1
2
TMX-0100 (Thermolinx™ Wi-fi Module) Procedure Installation
The TMX-0100 is designed to be used with the ZON-0550 and ThermoLinx App for remote access. The
operational status of the TMX-0100 is indicated by lights (LEDs). The TMX-0100 has three (3) lights on the front
(Red for Wi-Fi, Green for Ready, Blue for Server). Information is communicated by the color of the lights and
whether they are steady or flashing.
The unit should be installed inside and protected from falling water and high humidity conditions. With all the
covers in place, it is designed to protect any individual from accidental electrical shock. It is not suitable for
installation in hazardous locations and should not be close to any electromagnetic fields.
Installation
1. Connect the CAB-0150 connector to the Wi-Fi port of the ZON-0550 on the right side of the control.
The Cab-0150 connector length cannot be extended and no other connector shall be used for
installation.
2. Connect the TMX-0100 to the CAB-0150 connector.
WIfI sysTeM seTUP
Zon-0550
TMX-0100
Cab-0150