Functions and outputs
HBM
QuantumX
Note
In general, a CAN network enables both message types (standard/extended) to be
used.
No analysis of Sync messages or Remote frames is made.
The four CAN nodes are handled with equal priority.
A node parameterized as sender, works as an autonomous gateway and does no
longer require connection to a PC.
SDOs are not supported; the MX471 can thus not be considered as a CANopen slave.
The individual nodes’ statuses are directly displayed at the respective connection
point.
CAUTION
If a CAN node uses an incorrect baud rate for transmission over the bus, the entire
data transmission on the bus may fail.