Manual parameterization and configuration
ML77B
A00760_09_E00_00
HBM: public
47
11.1.1 Device parameterisation entry
Byte
no.
Bit no.
Meaning
Default
0
Byte
Reserved
0
1..2
16-bit
Enable diagnosis for channels 1..16
0xFFFF (enabled)
11.1.2 Parameterisation entry for 1-channel device
Byte
no.
Bit no.
Meaning
Default
0
Bit 0..3
Type: 1-channel
1 (const)
0
Bit 4..7
Data format
0 = Signed16 2 bytes
1 = Signed32 4 bytes
2 = Float (IEEE format) 4 bytes
3 = Float (Siemens format) 4 bytes
4 = Raw data (0..7680000) 4 bytes
5 = Raw data (0..30000) 2 bytes
0
1
Byte
Number of decimal places
acc. to dis
play
2
Bit 0..2
Enable PAR1..3 control bits in control word
0 (disabled)
2
Bit 3..5
Reserved
2
Bit 6
Enable MOMPEAK1 control bit in control word
0 (disabled)
2
Bit 7
Enable MOMPEAK2 control bit in control word
0 (disabled)
3
Bit 0
Enable BusOff control bit in control bit
0 (disabled)
3
Bit 1
Enable ACAL control bit in control word
0 (disabled)
3
Bit 2
Enable TAR control bit in control word
0 (disabled)
3
Bit 3
Enable NULL control bit in control word
0 (disabled)
3
Bit 4
Enable CLRPEAK1 control bit in control word
0 (disabled)
3
Bit 5
Enable CLRPEAK2 control bit in control word
0 (disabled)
3
Bit 6
Enable HLDPEAK1 control bit in control word
0 (disabled)
3
Bit 7
Enable HLDPEAK2 control bit in control word
0 (disabled)