HB-100/140/160Z1
Temperature Control Unit
Operation
O8285-EN 2017-12
77
8.6.2 Mould evacuation
Fig. 46: Setting mould evacuation time
If necessary, before switching on mould evacuation, set the
desired mould evacuation duration:
1.
Display the menu page
Setting \ Miscellaneous
.
2.
Set parameter
Time mould evacuation
to the desired value.
Fig. 47: Switch on mould evacuation
Switch on mould evacuation as follows:
1.
Display menu page
Functions
.
2.
Select the function
Mould evacuation
and activate with the
key.
The activated function is indicated with the
symbol.
Cooling down to 70 °C takes place before the mould
evacuation process.
Consumers and supply hoses are sucked empty and
depressurised.
Afterwards, the temperature control unit is switched off.
NOTE!
Before opening connections between the
temperature control unit and the consumer, check
that the pressure is 0 bar.
The evacuation volume is led to the cooling or
system water outlet.