7.3.3. ”bri” parameter
7.3.4. ”HOLd” menu
For example if input is set to “4-20” mode, the lower border is calculated to expression: Imin = 4 mA
- 4 mA × “Lo r” %. The “Lo r” value can be set from 0 to 99.9%. Parameter “Hi r” determines the upper
border of the permissible range accordingly to the expression (for all modes). For example if input is
set to “4-20” mode, then upper border is calculated due to expression: Imax = 20 mA + 20 mA × “Hi
r” %. The value of “Hi r” can be set from 0 to 19.9%
This parameter allows user to set bright of the LED display, bright can be set to conventional values from
1 to 8.
This menu contains parameters connected with peak detection function. See also full description of the
peak detection function in paragraph: DETECTION OF THE PEAK VALUES “mo
dE” - the type of detected
changes of the input signal, can be set to values:
If the measurement value do not exceeds permissible measurement range but displayed
value exceeds range -999 - 9999, the warning ”-Ov-” is displayed rather than the calculated
result.
peaks, peak and next drop of the input signal of value equal at least “PEA”,
”norm”
type of displayed values
“HdiS”
drops, drop and next peak of the input signal of value equal at least “PEA”
”inv”
”PEA”
maximum time to display of the peak (drop) value, the value can be set from 0.0 to
19.9 sec, with a 0.1 sec. resolution. If "HdiS”=”HOLD” then sett parameter
"timE"=0.0 will peak value until [ESC] button is pressed. If "HdiS”=”rEAL” then the
value "timE"=0.0 will not be hold.
“timE”