Troubleshooting
The following table lists possible faults and measures to eliminate these. Contact the manufacturer in
case of faults that cannot be remedied by following the descriptions here.
Fault
Possible cause
Test
Remedy
Operation outside the
permitted temperature range
Operate the battery pack within
the permitted temperature range.
Failure to pre-charge
Read the CAN messages
.
Incorrect assignment
of the signal module
Check for correct assignment
and correct cabling
see "Plug assignment", page 37
Excessive cell difference
Release the battery pack
and operate it for several
hours without load.
Over-discharge or deep discharge
If the battery pack
suffers deep discharge,
replace it. Contact HAWE.
If the battery pack is
overcharged, discharge it.
Battery pack does not respond
Defective fuse
Read the CAN messages
Replace the battery pack.
Contact HAWE.
Operation outside the
permitted current range
Operate the battery pack within
the permitted current range.
see "Current monitoring", page 13
Operation outside the
permitted temperature range
Read the CAN messages
Operate the battery pack within
the permitted temperature range.
Incorrect assignment
of the signal module
Check for correct assignment and
correct cabling
see "Plug assignment", page 37
Excessive cell difference
Release the battery pack
and operate it for several
hours without load.
Over-discharge or deep discharge
If the battery pack
suffers deep discharge,
replace it. Contact HAWE.
Battery pack switches
off whilst in operation
Defective fuse
Read the CAN messages
Replace the battery pack.
Contact HAWE.
Operation outside the
permitted temperature range
Operate the battery pack within
the permitted temperature range.
Failure to pre-charge
, pre-discharge
Battery pack not charging
Over-discharge or deep discharge
Read the CAN messages
If the battery pack
suffers deep discharge,
replace it. Contact HAWE.