3.5 Connector assignment
Connector assignment, voltage range of the start signal and electrical performance data are
detailed in the appendix under
1
Power module minus
2
Signal module
3
Power module plus
3.6 Number of cycles
The number of cycles (cycle life performance) is strongly dependent on the loading of the battery
and the conditions (temperature, charging currents and discharge currents) under which it is used. A
partial discharge of the battery reduces the loading and extends its service life, as does a partial charge.
Elevated temperatures and high currents have a negative effect on the cycle life performance.
■
IEP 014-CP: Set to 3.98 V per cell. This guarantees a higher number of cycles. If desired the charge
cut-off voltage can be raised to 4.20 V, which creates a penalty against the achievable number of
cycles.
The following values serve as indications. No more exact conclusion can be reached until the
relevant proles of load, charge and temperature prole can be tested at the battery for the
application in question.
Charge status (V/cell)
Discharge cycles
available stored energy in %
4,20
300 - 500
100
4,15
400 - 700
90 - 95
4,10
600 - 1000
85 -90
4,05
850 - 1500
80 -85
4,00
1200 – 2000
70 -75
3,90
2400 – 4000
60 -65