HAUBER-Elektronik GmbH
19
15.3
Limit values and delay times
SET
Position
Limit values (g)
Measuring
range
0-1 g
0-2 g
0-4 g
0-6 g
0-8 g
0-10 g
0
0
0
0
0
0
0
1
0.063
0.125
0.25
0.375
0.5
0.625
2
0.125
0.25
0.5
0.75
1
1.25
3
0.188
0.375
0.75
1.125
1.5
1.875
4
0.25
0.5
1
1.5
2
2.5
5
0.313
0.625
1.25
1.875
2.5
3.125
6
0.375
0.75
1.5
2.25
3
3.75
7
0.438
0.875
1.75
2.625
3.5
4.375
8
0.5
1
2
3
4
5
9
0.563
1.125
2.25
3.375
4.5
5.625
10
0.625
1.25
2.5
3.75
5
6.25
11
0.688
1.375
2.75
4.125
5.5
6.875
12
0.75
1.5
3
4.5
6
7.5
13
0.813
1.625
3.25
4.875
6.5
8.125
14
0.875
1.75
3.5
5.25
7
8.75
15
0.938
1.875
3.75
5.625
7.5
9.375
The
SET rotary button
has 16 positions, representing the limit value of an alarm. The
measuring range of the vibration monitoring unit is divided into 16 linear steps.
In general:
𝑙𝑖𝑚𝑖𝑡 𝑣𝑎𝑙𝑢𝑒 =
𝑢𝑝𝑝𝑒𝑟 𝑙𝑖𝑚𝑖𝑡 𝑚𝑒𝑎𝑠𝑟𝑢𝑖𝑛𝑔 𝑟𝑎𝑛𝑔𝑒
16
× 𝑆𝐸𝑇 𝑝𝑜𝑠𝑖𝑡𝑖𝑜𝑛
Example:
Limit setting
Measuring range:
0
–4 g
SET rotary button Pos.: 8 (9)
Limit value:
2 g (2.25 g)
Delay times
TIME Position
0
1
2
3
4
5
6
7
8
9
10
11 12 13 14 15
Delay time
(secs)
0
1
2
3
4
5 7.5 10 12.5 15 17.5 20 25 30 45 60
Tab. 6: Delay times