7 Block OUTPUTS
Device Functions Proline Promag 55
66
Hauser
7.1.2
Function group OPERATION
OUTPUTS
E
⇒
CURRENT OUTPUT 1
EAA
⇒
CONFIGURATION
400
⇓
⇓
OPERATION
404
CURRENT OUTPUT 2
EAB
⇒
CONFIGURATION
400
⇓
OPERATION
404
Function description
OUTPUTS
➞
CURRENT OUTPUT (1 to 2)
➞
OPERATION
ACTUAL CURRENT
(4040)
Use this function to view the computed actual value of the output current.
User interface:
0.00 to 25.00 mA
SIMULATION CURRENT
(4041)
Use this function to activate simulation of the current output.
Options:
OFF
ON
Factory setting:
OFF
!
Note!
• The "SIMULATION CURRENT OUTPUT" message indicates that simulation is active.
• The measuring device continues to measure while simulation is in progress, i.e. the
actual measuring values are output correctly via the other outputs.
"
Caution!
The setting is not saved if the power supply fails.
VALUE SIMULATION
CURRENT
(4042)
!
Note!
The function is not visible unless the SIMULATION CURRENT function (4041) is active
(= ON).
Use this function to define a freely selectable value (e.g. 12 mA) to be output at the
current output. This value is used to test downstream devices and the measuring device
itself.
User input:
0.00 to 25.00 mA
Factory setting:
0.00 mA
"
Caution!
The setting is not saved if the power supply fails.
Summary of Contents for Proline Promag 55
Page 2: ...Device Functions Proline Promag 55 2 Endress Hauser ...
Page 5: ...Device Functions Proline Promag 55 Contents Endress Hauser 5 ...
Page 164: ...14 Index Device Functions Proline Promag 55 164 Endress Hauser ...
Page 166: ...www endress com worldwide BA120D 06 en 10 09 71104957 FM SGML6 0 ...