8 Block INPUTS
Device Functions Proline Promag 55
106
Hauser
8.1.2
Function group OPERATION
INPUTS
F
⇒
STATUS INPUT
FAA
⇒
CONFIGURATION
500
⇓
OPERATION
504
Function description
INPUTS
➞
STATUS INPUT
➞
OPERATION
ACTUAL
STATUS INPUT
(5040)
Use this function to view the current level of the status input.
User interface:
HIGH
LOW
SIMULATION STATUS
INPUT
(5041)
Use this function to simulate the status input, i.e. to trigger the function (see function
ASSIGN STATUS INPUT (5000) on Page 105) assigned to the status input.
Options:
OFF
ON
Factory setting:
OFF
!
Note!
• The "SIMULATION STATUS INPUT" message indicates that simulation is active.
• The measuring device continues to measure while simulation is in progress, i.e. the
actual measuring values are output correctly via the other outputs.
"
Caution!
The setting is not saved if the power supply fails.
VALUE SIMULATION
STATUS INPUT
(5042)
!
Note!
The function is not visible unless the SIMULATION STATUS INPUT function (5041) is
active (= ON).
Use this function to define the level to be assumed at the status output during the
simulation. This value is used to test downstream devices and the flowmeter itself.
Options:
HIGH
LOW
Factory setting:
LOW
"
Caution!
The setting is not saved if the power supply fails.
Summary of Contents for Proline Promag 55
Page 2: ...Device Functions Proline Promag 55 2 Endress Hauser ...
Page 5: ...Device Functions Proline Promag 55 Contents Endress Hauser 5 ...
Page 164: ...14 Index Device Functions Proline Promag 55 164 Endress Hauser ...
Page 166: ...www endress com worldwide BA120D 06 en 10 09 71104957 FM SGML6 0 ...