
FAX 5/10/20/30/40KW
October 28, 2013
1
‐
19
888
‐
2720
‐
001
WARNING:
Disconnect
primary
power
prior
to
servicing.
Copyright
©2013,
Harris
Broadcast
1.10 Selecting Location for Transmitter Placement
Selecting
a
good
location
for
the
transmitter
to
be
placed
is
very
important.
There
are
several
points
that
should
be
considered
if
the
transmitter
is
in
a
new
location
or
being
moved
to
a
new
building.
Read
through
each
point
to
ensure
a
proper
and
safe
installation.
•
Make
sure
doors
into
the
site
are
large
enough
to
accommodate
the
transmitter.
Doorway
height
can
some
‐
times
be
a
problem.
If
the
doors
are
not
tall
enough
extra
manpower
may
be
required
to
get
the
transmitter
tipped
down
to
clear
the
door.
•
Ensure
the
floor
where
the
transmitter
is
to
be
placed
can
support
the
weight
of
the
transmitter.
See
the
ECM
sheets
in
this
section
for
dimensions
and
weight
of
your
model.
•
The
location
should
be
selected
so
there
is
enough
clearance
around
the
transmitter
with
the
doors
open
to
meet
local
electrical
and
safety
codes.
•
Breakers
and
or
disconnects
should
be
within
sight
of
the
transmitter.
If
possible
the
best
location
is
directly
behind
the
transmitter
on
the
wall.
•
Proper
lightning
protection
should
be
installed
in
the
building
by
a
professional
electrical
contractor.
Ensure
that
it
is
installed
as
close
to
the
AC
Mains
entrance
into
the
building
as
well
as
close
to
the
station
reference
ground.
•
If
the
transmitter
is
installed
in
a
high
RF
environment,
it
is
a
good
practice
to
utilize
cable
ferrites
on
all
con
‐
ductors
to
minimize
RF
interference.
•
Do
not
install
the
transmitter
in
places
where
it
may
be
exposed
to
mechanical
shocks,
excessive
vibration,
dust,
water,
salty
air,
or
acidic
gas.
•
If
outside
air
is
brought
into
the
building
it
should
be
well
filtered
to
keep
dirt
out
of
the
building
and
the
transmitter.
See
Section
1.11
Cooling
for
further
details.
•
Ambient
temperature
and
relative
humidity
should
always
range
between
the
following
limits
at
the
installa
‐
tion
location:
Ambient
temperature:
0
to
+45
o
C
Relative
humidity:
5
to
95%
non
‐
condensing
Note
Failure to follow these installation instructions may void the warranty.
•
Plan
the
RF
transmission
line
runs
so
that
a
minimum
number
of
elbows
are
required,
this
will
allow
for
best
performance.
It
is
usually
best
to
install
the
RF
line
first,
since
it
is
easier
to
work
around
it
with
the
AC
con
‐
duits
and
the
air
handling
duct.
1.11
Cooling
Flexiva
series
transmitters
use
forced
air
cooling
provided
by
multiple
internal
blowers
to
remove
the
heat
generated
by
the
signal
generation
and
amplification
processes.To
avoid
operational
problems
due
to
excessive
temperature,
the
blower
openings
must
not
be
blocked.
The
transmitter
Outline
Drawing
843
‐
5614
‐
103
provides
an
indication
of
the
relative
location
of
the
transmitter
blowers
and
the
necessary
clearances
to
respect.
Air
input
is
from
the
transmitter
front
with
hot
air
exhaust
at
the
rear
of
the
amplifier.
When
factory
rack
integration
has
been
provided,
the
exhaust
air
exits
through
a
vent
at
the
top
of
the
rack.
An
optional
intake
plenum
is
available
for
Harris
Broadcast
supplied
racks
to
permit
connection
to
an
external
ducted
air
system
at
the
top
of
the
rack
if
desired.
When
the
transmitter
components
are
mounted
in
a
customer
supplied
rack,
care
must
be
taken
not
to
overheat
the
other
pieces
of
equipment
already
installed
in
the
rack.
The
exhaust
from
the
Flexiva
amplifier
chassis
will
typically
be
10
o
C
to
20
o
C
hotter
than
the
ambient
air.
In
many
cases,
this
may
necessitate
use
of
a
vented
rear
rack
door
or
removal
of
rear
rack
door
altogether.
Additionally,
sufficient
rear
clearance
must
be
left
behind
the
Flexiva
amplifier
chassis
exhaust
ports,
typically
15cm
(6
in.)
or
greater.
Summary of Contents for Flexiva FAX 10KW
Page 2: ......
Page 8: ......
Page 10: ...WARNING Disconnect primary power prior to servicing ...
Page 167: ......