Chapter 4 –
Ways to Set
Scale Parameters
Hardy Process Solutions HI 6200 Weigh Processor User Guide
32
4.2.1 Saving “Known Good” Parameters
You can save the HI 6200 configuration to a different location in memory in order to restore
the configuration if it becomes compromised.
1. Open a web browser on the computer, enter the static IP address of the HI 6200
instrument that you set in a previous step (for example: the factory default is
192.168.000.100), and press the Enter key. The Home page appears (see Figure 4-1 on
page 31).
2. Click
Configuration
, and then click
Diagnostics
.
3. Click
Parameters
.